Sensors Activating Service Signal (H4/U6) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
27.6
Action
"Access"
Scroll to menu H4.
"A"
Scroll to menu U6.
"A"
"Return"
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x

Sensors activating SERVICE signal (H4/U6)

Service signal is indicated by LED "Service" (L12). The sensor week
average value is below or over the service level respectively for one or
more sensors. (Regarding the service signal levels, see Planning
Instructions, chapter "Service signal".
Menu H4/U6 is a list of the sensor(s) activating service signal.
NOTE! Service signal is only information that the sensors have to be
cleaned / replaced soon. The service signal has to be acknowledged,
see chapter "Acknowledge SERVICE signal (H8/S4)", page 145.
It is not possible to get a print-out from menu H4/U6.
Text in display
Present system status on display and
printer
Disablement
Printout: (1=yes)
Sensors activating SERVICE signal
Sensor : xxxxxx needs service
Sensors activating SERVICE signal
ACCEPT? H4
122
Comments
According to chapter
"Access", see page 92.
U1
Press "A" to accept.
U6
L = a list in which you
L
can scroll. Press "Return"
to menu U6. (If there are
no sensors in the list,
menu U6 will be shown
again.).
Scroll or press "Return"
U6
to menu H4. Scroll or
press "Return" to log off.