Invertek Drives Optidrive iE3 Technical Manual page 32

Ac variable speed drive 0.37kw – 22kw / 0.5hp – 30hp 110 – 480 volt 1 & 3 phase
Table of Contents

Advertisement

4.6.2
Modbus RTU / CAN Open Index – Parameters
Modbus
CAN
RTU
Open
Par.
Register
Index
129
2065h
01
Max speed limit
130
2066h
02
Min speed limit
131
2067h
03
Accel ramp time
132
2068h
04
Decel ramp time
2069h
133
05
Stop Mode
206Ah
134
06
Energy Optimiser
206Bh
135
07
Motor rated voltage
136
206Ch
08
Motor rated current
137
206Dh
09
Motor rated frequency
138
206Eh
10
Motor rated speed
139
206Fh
11
Boost Value
2070h
140
12
Control mode
2071h
141
13
Application Mode
142
2072h
14
Access code
143
2073h
15
Digital input function
2074h
144
16
Analog input format
2075h
145
17
Effective switching frequency
146
2076h
18
Relay Output Function
147
2077h
19
Digital Threshold
148
2078h
20
Preset Speed 1
149
2079h
21
Preset Speed 2
150
207Ah
22
Preset Speed 3
151
207Bh
23
Preset Speed 4
nd
152
207Ch
24
2
153
207Dh
25
Analog Output Function
154
207Eh
26
Skip Frequency Centre
155
207Fh
27
Skip Frequency Band
156
2080h
28
V/F Adjust Voltage
157
2081h
29
V/F Adjust Frequency
158
2082h
30
Start Mode Select
159
2083h
31
Keypad restart mode
160
2084h
32
DC Injection
161
2085h
33
Spin Start Enable
162
2086h
34
Brake circuit enable
163
2087h
35
Analog Input / Slave Scaling
164
2088h
36
Communication Settings
165
2089h
37
Access code definition
208Ah
166
38
Parameter lock
167
208Bh
39
Analog input offset
168
208Ch
40
Display Scaling Function
169
208Dh
41
User PI P gain
170
208Eh
42
User PI I time constant
171
208Fh
43
User PI mode select
Optidrive E3 Advanced Technical Manual Issue 05.Docx
Description
Format
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
Ramp
U16
U16
U16
U16
U16
U16
WORD
U16
WORD
U16
U16
U16
WORD
U16
U16
U16
WORD
U16
U16
U16
Min
Max
0
5*P-09
0
P-01
0
60000
0
60000
0
3
0
1
0
250
500
0
Drive Rating Dependent
25
500
0
60 * P-09
0
Drive Rating Dependent
0
6
0
2
0
9999
0
17
0
7
0
5
(Drive Rating Dependent)
0
9
0
1000
-P-01
P-01
-P-01
P-01
-P-01
P-01
-P-01
P-01
0
60000
0
10
0
P-01
0
P-01
0
P-07
0
P-09
See Below
0
7
See Below
0
2
0
4
0
20000
See Below
0
9999
0
1
-5000
5000
See Below
1
300
0
300
0
1
Data format / scaling
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
2dp, e.g. 300=3.00s
2dp, e.g. 300=3.00s
0: Ramp to stop + Mains Loss Ride Through
1: Coast to stop
2: Ramp to stop + Fast Stop
3 : AC Flux Braking + Fast Stop
0: Disabled
1: Enabled
400 = 400 Volts
1dp, e.g. 100 = 10.0A
Data unit is in Hz
RPM
1dp, e.g. 100 = 10.0%
0: Terminal Control
1: Keypad forward only
2: Keypad forward and reverse
3: Modbus control mode
4: Modbus control with ramp control
5 : PID control
6 : PID control with analog speed sum
7 : CAN Open
8 : CAN Open + Ramp Control
9 : Slave Mode
0 : Industrial Mode
1 : Pump Mode
2 : Fan Mode
No Scaling
See section 2.6 for function details
0: 0...10V
1: b 0...10V
2: 0...20mA
3: t 4...20mA
4: r 4...20mA
5: t 20...4mA
6: r 20...4mA
7 : 10...0V
0 = 4KHz
1 = 8KHz
2 = 12Khz
3 =16KHz
4 = 24KHz
5 = 32KHz
See parameter description for details
100 = 10.0%
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
2dp e.g. 250 = 2.50s
See user guide for function details
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
100 = 100V
50 = 50Hz
See parameter description for details
See parameter description for details
See parameter description for details
1000 = 100.0%
0: Unlocked
1: Locked
1dp, e.g. 300=30.0%
1dp, e.g. 10 = 1.0
1dp, e.g. 10 = 1.0s
See parameter description for details
33 / 69