7.28 Submenu for manual test run
S U B M E N U
TEST RUN man.
7.28.1 Activate manual test run
TEST RUN man.
The function and operation of the started manual test run is similar to the automatic
test run
Press
on the Hydrovar-Smart to change to
7.28.2 Test Frequency
TEST-FREQUENCY
30.0 Hz
Press
on the Hydrovar-Smart to change to
To leave the submenu press the
S U B M E N U
TEST RUN man.
Press
on the Hydrovar-Smart to change to
7.29 Submenu - Error
S U B ME N U
ERRORS
7.29.1 Conveyor Limit
CONVEYOR-LIMIT
disabled
"disabled" or "0 bar" is shown on the display.
An adjusted value >0 has to be reached till the programmed "DELAY TIME".
Doesn't this value be reached; the failure "VAL. RANGE CONTR." will be indicated and
the pump stops.
Press
on the Hydrovar-Smart to change to
Press
and the display changes to
By simultaneously pressing
+
be released.
Frequency for manual and automatic test run.
Can be set from 6.0 Hz up to 70,0 Hz
longer than 3 sec. to change to
Press
and the display changes to
Disabled or adjustable between 0.00...SENSOR
RANGE. To disable the conveyor limit, press
for about 3 seconds to enter the submenu
for about 3 seconds to enter the submenu
37
+
a test run will
till