Chapter 6. COMMREQ/Data_Init_Comm Programming
6.4.14 COMMREQ #23: Write Map Command
To set the reference table mapping of a 90-70 Remote Scanner on the Genius bus, use the
Write Map command.
Command Block for the Write Map Command
Address
Address +1
Address +2
Address +3
Address +4
Address +5
Address +6
Address +7
Address +8
Address +9
to
Address +16
72 Public
PACSystems RX3i Genius Communications Gateway User Manual
Command Length
No Wait
Status Block memory type
Status Block offset
Idle timeout value
Max. communications time
Command number
PROFINET Device number
Genius Device Number
Data to be written to the
target device.
11
0
70 (%I), 72 (%Q), 8 (%R), 10 (%AI), 12 (%AQ) or 196 (%W)
Beginning address for the COMMREQ Status Block.
0
0
23
1-255: The device number of the targeted GCG Genius Gateway.
0-31: the SBA of the targeted Genius Device to which data is to be
transmitted.
Same format as Read Map Returned Data described above.
The checksums will be ignored.