Types of PROFINET Communications
Genius Communications Gateways use two types of PROFINET communication transfers: real-
time and non-real-time. The illustration below shows real-time communications as solid lines
and non-real-time communications as dashed lines.
Real-Time (RT) communication: PROFINET real-time communication is used for time-sensitive
data. A PROFINET IO-Controller (PROFINET Controller) and PROFINET IO-Device use two types
of real-time communications to exchange data: cyclic communication and acyclic
communication:
Real-time Cyclic communication is used to periodically transfer the application's input
and output data. Cyclic communication occurs each PROFINET IO production cycle.
Real-time Acyclic communication is used to transfer non-periodic data such as alarms.
Acyclic communication occurs only when needed.
Non-Real-Time (NRT) communication: PROFINET non-real-time communication is used for
less time-sensitive data such as configuration, parameterization, diagnostics, and
identification data.
Operations of the Genius Communications Gateway
The Genius Communications Gateway performs the following operations:
Consumes PROFINET IO-Device configuration from the PROFINET IO-Controller over the
PROFINET network.
Scans input data from each Genius device it manages and produces that data to the
PROFINET IO-Controller.
Consumes the output data that it receives from the PROFINET IO-Controller and applies it
to each Genius device it manages.
Where needed, translates Genius Datagrams (background traffic) into PROFINET
packages that are sent to the PROFINET Controller. This includes Datagrams that
originated at the Genius Devices, such as Fault Reports.
Translates PROFINET packages that are sent by the PROFINET Controller into Genius
Datagrams. This includes Datagrams that originated at the PLC through use of COMMREQ
or Data_Init_Comm instructions. For example, a COMMREQ is used to generate a Clear
Fault Report datagram.
GFK-2892B
RX3i with PROFINET Controller (PNC)
1
OK
2
LAN
3
STAT US
4
CONN
PNS001
TO INSTALL,
TORQUE TO
6 IN -LB.
ACTIVE
USB
IP ADDRESS
MAC ADDRESS
PORTS
FRONT
3 4
1 2
IO DEVICE
Real-Time Data
Inputs
Outputs
Alarms
Figure 6: Real-Time & Non-Real-Time Data Types
PACSystems RX3i Genius Communications Gateway User Manual
Non Real-Time
Data
Parameters
Configuration Data
Chapter 1. Introduction
Public 13

Advertisement

Table of Contents
loading

Table of Contents