Product Overview; Figure 2: Gcg001 Module - GE PACSystems RX3i Genius User Manual

Programmable control products, communications gateway
Table of Contents

Advertisement

Chapter 1. Introduction
1.2

Product Overview

Features of the GCG001 module include:
Attachment of two RJ-45 Ethernet connections (Ports 1 & 2)
Support for both star (switched) and linear (daisy-chained) network
topologies
Supports Ethernet Media Redundancy Protocol (MRP)
LEDs to indicate Ethernet status (ACT & LINK)
Attachment Genius bus connections
Supports Genius Redundancy consisting of a single Genius bus with
two GCG001 Gateways, one at SBA #30 and the other at SBA #31.
No other form of Genius redundancy is supported.
LED to indicate Genius Communications Status (COM)
LEDs to indicate module status (refer to module header)
Panel-mount (typical)
Optional mounting in RX3i expansion slot
Cable tie-down loop on underside of module (at front)
24Vdc power connector on underside of module
0.2A maximum current draw
Secure Digital (SD) Card Slot, accessible at rear of module
Firmware load pushbutton, accessible at rear of module
Note: Although the hardware supports the 10/100BASE TX Ethernet standard, PROFINET I/O
over wired infrastructure must be 100Mbps full-duplex or faster. 10Mbps should not be
used for PROFINET.
8 Public
PACSystems RX3i Genius Communications Gateway User Manual
POWER
OK
FAULT
CONNECT
GCG001
ETHERNET
COM
SER 1
SER 2
SHLD
SHLD
OUT
IN
GENIUS

Figure 2: GCG001 Module

GFK-2892B

Advertisement

Table of Contents
loading

Table of Contents