Chapter 1. Introduction
1.2
Product Overview
Features of the GCG001 module include:
•
Attachment of two RJ-45 Ethernet connections (Ports 1 & 2)
•
Support for both star (switched) and linear (daisy-chained) network
topologies
•
Supports Ethernet Media Redundancy Protocol (MRP)
•
LEDs to indicate Ethernet status (ACT & LINK)
•
Attachment Genius bus connections
•
Supports Genius Redundancy consisting of a single Genius bus with
two GCG001 Gateways, one at SBA #30 and the other at SBA #31.
No other form of Genius redundancy is supported.
•
LED to indicate Genius Communications Status (COM)
•
LEDs to indicate module status (refer to module header)
•
Panel-mount (typical)
•
Optional mounting in RX3i expansion slot
•
Cable tie-down loop on underside of module (at front)
•
24Vdc power connector on underside of module
•
0.2A maximum current draw
•
Secure Digital (SD) Card Slot, accessible at rear of module
•
Firmware load pushbutton, accessible at rear of module
Note: Although the hardware supports the 10/100BASE TX Ethernet standard, PROFINET I/O
over wired infrastructure must be 100Mbps full-duplex or faster. 10Mbps should not be
used for PROFINET.
8 Public
PACSystems RX3i Genius Communications Gateway User Manual
POWER
OK
FAULT
CONNECT
GCG001
ETHERNET
COM
SER 1
SER 2
SHLD
SHLD
OUT
IN
GENIUS
Figure 2: GCG001 Module
GFK-2892B