Chapter 3
Configuration
The RX3i GCG001 Genius Gateway receives its configuration via its connected PROFINET I/O
Controller (PROFINET Controller). The PROFINET Controller, in turn, is configured by a PROFINET
I/O configuration tool. This tool will require a GSDML file for the GCG001 Genius Gateway. The
RX3i GCG001 GSDML can be obtained from GE's Automation and Controls support website,
http://www.geautomation.com, using GCG001 as your search term. For subsequent use,
import the RX3i GCG001 GSDML file into the Tool Chest of Proficy Machine Edition.
3.1

Configuration Tools

PACSystems RX3i CPU Firmware 8.00 or later.
Proficy Machine Edition configuration and programming software, version 8.0 or later.
Serial or Ethernet cable for connecting the Proficy Machine Edition programmer computer
to the RX3i CPU.
General Station Description Markup Language (GSDML) file for the GCG001, available from
GE's Automation and Controls support website,

3.2 Configuration Overview

The steps involved in configuring a GCG001 Genius Gateway are as follows:
1.
If you haven't already done so, use Machine Edition to add a PROFINET IO-Controller
(IC695PNC001) to the Hardware Configuration of the target control system.
2.
Select the PNC001 in the Navigator window, then browse the module and the Local Area
Network (LAN) configuration in the Inspector window, changing parameters as necessary
for your system. Note that the GCG001 will operate at 100Mbps, and will cause the
Network Speed to be auto-negotiated to this speed.
3.
Right-click the PNC001, then select Add IO-Device to add the GCG001 as a connected
device on the PROFINET LAN. In the PROFINET Device Catalog dialog that subsequently
appears, select Have GSDML..., then browse to the location on your computer where the
file is located, select it, and Open. As mentioned above, the GSDML can be conveniently
stored in the PME Tool Chest.
4.
Use PROFINET/DCP tool in Machine Edition to assign a name to the GCG001 Gateway so
that the PROFINET Controller can connect to it and send its configuration. To do this, right-
click the PNC001, then select Launch Discovery Tool GCG001.The tool will appear in a
new InfoViewer tab entitled PROFINET DCP – Direct Connection (see Figure 12).
Note:
5.
With the GCG001 connected to the PNC001 via Ethernet cables, and both the RX3i rack
and the GCG001 powered up, select Refresh Device List. Find the GCG001 in the list. If its
Device Name does not match the Device Name configured on the PNC001 , select the
GCG001 , then select Edit Device, change the Device Name, then Exit.
6.
GeniusGateway... appears in the Device Catalog tree.
Select GeniusGateway, then OK.
7.
geniusgateway...
now appears
(Figure 14) as an
IO device in the
Hardware
Configuration
tree under the
GFK-2892B
This tool can also be activated from the Utilities tab in the Navigation pane
by selecting PROFINET DCP.
PACSystems RX3i Genius Communications Gateway User Manual
Chapter 3. Configuration
http://www.geautomation.com.
Figure 14: Hardware Configuration
Expanded Tree
Public 29