Commreq #23: Write Map Command - GE GFK-2892F User Manual

Pacsystems rx3i genius communications gateway
Table of Contents

Advertisement

COMMREQ #23: Write Map Command

To set the reference table mapping of a 90-70 Remote Scanner on the Genius bus, use the Write Map
command.
Command Block for the Write Map Command
Address
Command Length
Address +1
No Wait
Address +2
Status Block memory type
Address +3
Status Block offset
Address +4
Idle timeout value
Address +5
Max. communications time
Address +6
Command number
Address +7
PROFINET Device number
Address +8
Genius Device Number
Address +9
Data to be written to the
to
target device.
Address +16
GFK-2892F
Chapter 6. COMMREQ/Data_Init_Comm Programming
11
0
70 (%I), 72 (%Q), 8 (%R), 10 (%AI), 12 (%AQ) or 196 (%W)
Beginning address for the COMMREQ Status Block.
0
0
23
1-255: The device number of the targeted GCG Genius Gateway.
1-29: the SBA of the targeted Genius Device to which data is to be
transmitted.
Same format as Read Map Returned Data described above.
The checksums will be ignored.
March 2019
81

Advertisement

Table of Contents
loading

Table of Contents