Download Print this page

Server Technology PRO2 User Manual page 235

Switched pdu
Hide thumbs Also See for PRO2:

Advertisement

Command Syntax
Command Access
Example
Chapter 8: Using the Command Line Interface (CLI)
show sensors
Switched PDU: show sensors
Sensor
ID
Sensor Name
------
--
-----------
Temp
A1
Temp_Sensor_A1
Temp
A2
Temp_Sensor_A2
Temp
C1
Temp_Sensor_C1
Temp
C2
Temp_Sensor_C2
Humid
A1
Humid_Sensor_A1
Humid
A2
Humid_Sensor_A2
Humid
C1
Humid_Sensor_C1
Humid
C2
Humid_Sensor_C2
Contact C1
Contact_Sensor_C1
Contact C2
Contact_Sensor_C2
Contact C3
Contact_Sensor_C3
Contact C4
Contact_Sensor_C4
Water
C1
Water_Sensor_C1
ADC
C1
ADC_Sensor_C1
SNMP
Sensor
ID
Notif.
------
--
------
Temp
A1
enabled
Temp
A2
enabled
Temp
C1
enabled
Temp
C2
enabled
Humid
A1
enabled
Humid
A2
enabled
Humid
C1
enabled
Humid
C2
enabled
Contact C1
enabled
Contact C2
enabled
Contact C3
enabled
Contact C4
enabled
Water
C1
enabled
ADC
C1
disabled
Common Sensor Settings
Temperature Scale:
Temperature Sensor Hysteresis:
Humidity Sensor Hysteresis:
ADC Sensor Hysteresis:
Email
Notif.
Lo-Alrm
------
-------
enabled
1C
enabled
1C
enabled
1C
enabled
1C
enabled
5% RH
enabled
5% RH
enabled
5% RH
enabled
5% RH
enabled
--
enabled
--
enabled
--
enabled
--
enabled
--
disabled
0
Celsius
1C
2% RH
1
PRO2 User Guide
Lo-Warn
Hi-Warn
Hi-Alrm
-------
-------
-------
5C
45C
50C
5C
45C
50C
5C
45C
50C
5C
45C
50C
10% RH
90% RH
95% RH
10% RH
90% RH
95% RH
10% RH
90% RH
95% RH
10% RH
90% RH
95% RH
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
0
255
255
235

Advertisement

loading
Need help?

Need help?

Do you have a question about the PRO2 and is the answer not in the manual?

Subscribe to Our Youtube Channel