Field Settings Table 1-2 - Daikin EGSQH10S18AA9W Service Manual

Ground source heat pump
Hide thumbs Also See for EGSQH10S18AA9W:
Table of Contents

Advertisement

ESIE13-03
|
Part 5. Appendix
Field settings table
Breadcrumb
Field code
Setting name
A.6.6
Are you sure you want to activate the forced defrost function?
Brine freezeup temperature
A.6.9
[A-04]
Boiler efficiency
A.6.A
[7-05]
Overview settings
A.8
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
A.8
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
A.8
[0-02]
High ambient temp. for LWT add zone heating WD curve.
A.8
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
A.8
[0-04]
--
A.8
[0-05]
--
A.8
[0-06]
--
A.8
[0-07]
--
A.8
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
A.8
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
A.8
[0-0D]
High ambient temp. for DHW WD curve.
A.8
[0-0E]
Low ambient temp. for DHW WD curve.
A.8
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
A.8
[1-01]
High ambient temp. for LWT main zone heating WD curve.
A.8
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
A.8
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
A.8
[1-04]
--
A.8
[1-05]
--
A.8
[1-06]
--
A.8
[1-07]
--
A.8
[1-08]
--
A.8
[1-09]
--
A.8
[1-0A]
What is the averaging time for the outdoor temp?
A.8
[2-00]
When should the disinfection function be executed?
A.8
[2-01]
Should the disinfection function be executed?
A.8
[2-02]
When should the disinfection function start?
A.8
[2-03]
What is the disinfection target temperature?
A.8
[2-04]
How long must the tank temperature be maintained?
A.8
[2-05]
Room antifrost temperature
A.8
[2-06]
Room frost protection
A.8
[2-09]
Adjust the offset on the measured room temperature
A.8
[2-0A]
Adjust the offset on the measured room temperature
A.8
[2-0B]
What is the required offset on the measured outdoor temp.?
A.8
[3-00]
Is auto restart of the unit allowed?
A.8
[3-01]
--
A.8
[3-02]
--
A.8
[3-03]
--
A.8
[3-04]
--
A.8
[3-05]
--
A.8
[3-06]
What is the maximum desired room temperature in heating?
A.8
[3-07]
What is the mimimum desired room temperature in heating?
A.8
[3-08]
--
A.8
[3-09]
--
A.8
[4-00]
What is the BUH operation mode?
A.8
[4-01]
--
A.8
[4-02]
Below which outdoor
temperature is heating allowed?
A.8
[4-03]
--
A.8
[4-04]
--
A.8
[4-05]
--
A.8
[4-06]
--
(*) This setting is not applicable for this unit. Do not change the default value.
13/05/15
|
Version 2.0
Figure 71 - Field settings table 1-2
Installer setting at variance with
default value
Range, step
Date
Value
Default value
R/W
(*)
R/W
0: 0°C
1: -2°C
2: -4°C
3: -6°C
4: -8°C
5: -10°C
6: -12°C
7: -14°C
R/W
0: Very high (*)
1: High
2: Medium
3: Low
4: Very low
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
R/W
[9-05]~[9-06]°C, step: 1°C
60°C
R/W
10~20°C, step: 1°C
15°C
R/W
-20~5°C, step: 1°C
-20°C
R/W
8
R/W
12
R/W
35
R/W
20
R/W
35~[6-0E]°C, step: 1°C
45°C
R/W
45~[6-0E]°C, step: 1°C
60°C
R/W
10~20°C, step: 1°C
15°C
R/W
-20~5°C, step: 1°C
-20°C
R/W
-20~5°C, step: 1°C
-20°C
R/W
10~20°C, step: 1°C
15°C
R/W
[9-00]~[9-01], step: 1°C
60°C
R/W
[9-00]~min(45,[9-01]), step: 1°C
25°C
R/W
0
R/W
0
R/W
20
R/W
35
R/W
22
R/W
18
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0: No
1: Yes
R/W
0~23 hour, step: 1 hour
23
R/W
60°C
R/W
60 min
R/W
4~16°C, step: 1°C
12°C
R/W
0: Disabled
1: Enabled
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: No
1: Yes
R/W
0
R/W
1
R/W
4
R/W
2
R/W
1
R/W
18~30°C, step: A.3.2.4
30°C
R/W
12~18°C, step: A.3.2.4
12°C
R/W
35
R/W
15
R/W
0: Limit
1: Enable
2: Only DHW
R/O
0
R/W
14~35°C, step: 1°C
35°C
R/W
3
R/W
2
R/W
0
R/W
0
Ground source heat pump
Field settings table
Breadcrumb
Field code
Setting name
A.8
[4-07]
Enable the second step of the backup heater?
A.8
[4-08]
Which power limitation mode is required on the system?
A.8
[4-09]
Which power limitation type is required?
A.8
[4-0B]
--
A.8
[4-0D]
--
A.8
[5-00]
Is backup heater or boiler operation allowed above equilibrium
temperature during space heating operation?
A.8
[5-01]
What is the equilibrium temperature for the building?
A.8
[5-02]
--
A.8
[5-03]
--
A.8
[5-04]
--
A.8
[5-05]
What is the requested limit for DI1?
A.8
[5-06]
What is the requested limit for DI2?
A.8
[5-07]
What is the requested limit for DI3?
A.8
[5-08]
What is the requested limit for DI4?
A.8
[5-09]
What is the requested limit for DI1?
A.8
[5-0A]
What is the requested limit for DI2?
A.8
[5-0B]
What is the requested limit for DI3?
A.8
[5-0C]
What is the requested limit for DI4?
A.8
[5-0D]
What type of backup heater installation is used?
A.8
[5-0E]
--
A.8
[6-00]
The temperature difference determining the heat pump ON temperature.
A.8
[6-01]
The temperature difference determining the heat pump OFF temperature.
A.8
[6-02]
--
A.8
[6-03]
What is the capacity of the backup heater step 1?
A.8
[6-04]
What is the capacity of the backup heater step 2?
A.8
[6-05]
--
A.8
[6-06]
--
A.8
[6-07]
--
A.8
[6-08]
Reheat hysteresis
A.8
[6-09]
--
A.8
[6-0A]
What is the desired comfort storage temperature?
A.8
[6-0B]
What is the desired eco storage temperature?
A.8
[6-0C]
What is the desired reheat temperature?
A.8
[6-0D]
What is the desired setpoint mode in DHW?
A.8
[6-0E]
What is the maximum tank temperature setpoint?
A.8
[7-00]
--
A.8
[7-01]
--
A.8
[7-02]
How many leaving water temperature zones are there?
A.8
[7-03]
PE factor
A.8
[7-04]
--
A.8
[7-05]
Boiler efficiency
A.8
[8-00]
Minimum running time for domestic hot water operation.
A.8
[8-01]
Maximum running time for domestic hot water operation.
A.8
[8-02]
Anti-recycling time.
A.8
[8-03]
--
A.8
[8-04]
Additional running time for the maximum running time.
A.8
[8-05]
Allow modulation of the LWT to control the room?
A.8
[8-06]
Leaving water temperature maximum modulation.
A.8
[8-07]
--
A.8
[8-08]
--
A.8
[8-09]
What is the desired comfort main LWT in heating?
A.8
[8-0A]
What is the desired eco main LWT in heating?
A.8
[8-0B]
--
A.8
[8-0C]
--
A.8
[8-0D]
--
A.8
[9-00]
What is the maximum desired LWT for main zone in heating?
A.8
[9-01]
What is the mimimum desired LWT for main zone in heating?
A.8
[9-02]
--
A.8
[9-03]
--
A.8
[9-04]
--
A.8
[9-05]
What is the mimimum desired LWT for add. zone in heating?
A.8
[9-06]
What is the maximum desired LWT for add. zone in heating?
A.8
[9-07]
--
(*) This setting is not applicable for this unit. Do not change the default value.
1. Field settings
Installer setting at variance with
default value
Range, step
Date
Value
Default value
R/W
0: No
1: Yes
R/W
0: No limitation
1: Continuous
2: Digital inputs
R/W
0: Current
1: Power
R/W
1
R/W
3
R/W
0: Allowed
1: Not allowed
R/W
-15~35°C, step: 1°C
0°C
R/O
0
R/W
0
R/W
10
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/O
4: 3PN,(1/2)
R/W
1
R/W
2~20°C, step: 1°C
2°C
R/W
0~10°C, step: 1°C
2°C
R/W
0
R/W
0~10kW, step: 0,2kW
3kW
R/W
0~10kW, step: 0,2kW
3kW
R/W
0
R/W
0
R/W
0
R/W
2~20°C, step: 1°C
10°C
R/W
0
R/W
30~[6-0E]°C, step: 1°C
60°C
R/W
30~min(50, [6-0E]) °C, step: 1°C
45°C
R/W
30~min(50, [6-0E]) °C, step: 1°C
45°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
60°C
R/W
0
R/W
2
R/W
0: 1 LWT zone
1: 2 LWT zones
R/W
0~6, step: 0,1
2,5
R/W
0
R/W
0: Very high
(*)
1: High
2: Medium
3: Low
4: Very low
R/W
0~20 min, step: 1 min
5 min
R/W
5~95 min, step: 5 min
30 min
R/W
0~10 hour, step: 0,5 hour
0,5 hour
R/W
50
R/W
0~95 min, step: 5 min
95 min
R/W
0: No
1: Yes
R/W
1~5°C, step: 1°C
3°C
R/W
18
R/W
20
R/W
[9-01]~[9-00], step: 1°C
55°C
R/W
[9-01]~[9-00], step: 1°C
45°C
R/W
13
R/W
10
R/W
10
R/W
37~65°C, step: 1°C
65°C
R/W
15~37°C, step: 1°C
24°C
R/W
22
R/W
5
R/W
1
R/W
15~37°C, step: 1°C
24°C
R/W
37~65°C, step: 1°C
65°C
R/W
5
Page 155