C1-01 Acceleration time 1
C1-02 Deceleration time 1
Setting Range:
Factory Default:
Acceleration time 1 sets the time necessary for the output frequency to accelerate from 0Hz to maxi-
mum output frequency as set in parameter E1-04. Deceleration time 1 sets the time necessary for the
output frequency to decelerate from the maximum output frequency to 0Hz.
D1-01 Preset Frequency Reference 1
D1-02 Preset Frequency Reference 2
D1-03 Preset Frequency Reference 3
D1-04 Preset Frequency Reference 4
Setting Range:
Factory Default:
Up to 4 preset speed references (including jog) can be set through multi-function contact input func-
tion selections in the Quick-Start mode. Terminals 6 and 7 are factory defaulted to multi-step speed
inputs 1 and 2, respectively. See the following table for programming preset speed references in the
Quick-Start mode.
Terminal 5
Open
Closed
Open
Closed
Note: 9 preset references can be set in the Advanced modes.
D1-09 Jog Frequency Reference
The jog frequency reference can be set in this parameter. In the Quick-Start mode, depress the
JOG key on the digital operator, or close terminal 7 when parameter H1-05 is set to "6", to use
this function. The jog command always has priority over other reference commands. When
using terminal 7 to select the jog frequency, a separate run command must be applied to run
the inverter.
VG5 Installation & Quick-Start Manual
0.00 to 6000.0s
10.0s
0.0 to 400.0Hz
0.0Hz
Terminal 6
Open
Speed Reference 1 - Set Reference Source (B1-01) to "0".
Speed Reference 2 (When H3-05 0 and H3-09 0)
Open
Closed
Speed Reference 3
Closed
Speed Reference 4
Chapter 3 - Quick-Start Programming
Control
Accel Time 1
Decel Time 1
Control
Reference 1
Reference 2
Reference 3
Reference 4
Speed Reference
Control
JOG Reference
Programming Menu
V/f
V/f
Open Loop
Flux
w/ PG
Vector
Vector






V/f
V/f
Open Loop
Flux
w/ PG
Vector
Vector












V/f
V/f
Open Loop
Flux
w/ PG
Vector
Vector


