Saftronics CIMR-VG5U Installation & Quick Start Manual page 100

Vg5 series revision f general purpose flux vector inverter with avc
Table of Contents

Advertisement

Appendix
VG5 Parameters
Name
Parameter
Function
(Digital Operator
No.
Display)
Station Address
H5-01
(Serial Comm Adr)
Communication
Speed Selection
H5-02
(Serial Baud Rate)
Communication
Parity Selection
H5-03
(Serial Com Sel)
Stopping Method
After Communica-
H5-04
tion Error
(Serial Fault Sel)
Timeover Detection
H5-05
(Serial Flt Dtct)
Motor Protection
Selection
L1-01
(MOL Fault Select )
Motor Protection
Time Constant
L1-02
(MOL Time Const)
Momentary Power
Loss Detection
L2-01
(PwrL Selection)
Momentary Power
Loss Ride Through
L2--02
(PwrL Ridethru t)
Min. Baseblock
Time
L2-03
(PwrL Baseblock t)
Voltage Recovery
Time
L2-04
(PwrL V/F Ramp t)
Undervoltage
Detection Level
L2-05
(PUV Det Level)
KEB Deceleration
Rate
L2-06
(KEB Frequency)
100
Setting
Setting
Factory
Range
Unit
Setting
(Digital Operator Display)
0~20
1
1F
0 : (1200 Baud)
1 : (2400 Baud)
0~4
0
3
2 : (4800 Baud)
3 : (9600 Baud)
4 : (19200 Baud)
0 : (No Parity)
0, 1, 2
1
0
1 : (Even Parity)
2 : (Odd Parity)
0: (Ramp to Stop)
1: (Coast to Stop)
0~3
1
3
2: (Fast - Stop)
3: (Alarm Only)
0 : (Disabled)
0, 1
1
1
1 : (Enabled)
0: (Disabled)
0, 1
1
1
1: (Coast to Stop)
When O2-09=1 [American
Spec] the setting range is
0.1~5.0
0.1~20min. The factory default
0.1 min.
1.0
min.
setting then becomes 8 min.
8 min. is the operation time
from a cold start.
0 : (Disabled)
1 : Power loss ride through
0, 1, 2
1
0
2 : (CPU Power Active)
** Factory setting differs
0.0~2.0
0.1s
0.7**
depending on inverter capacity
(02-04).
* Factory setting differs
depending on inverter capacity.
0.1~5.0
0.1s
0.5*
Lower limit of setting range is
changed from 0 to 0.1.
* Factory setting differs
0.0~5.0
0.1s
0.3*
depending on inverter capacity
(02-04).
*Voltage Class
150~
200V class=190V Det level
1V
190*
210
400V class=190V x 2= 380V level
575V class=190x575/200=546 level
0.0~
0.1%
0.0
100.0
Change
during
Remarks
Operation
o: Enabled
x: Disabled
x
x
<1110>
x
x
x
x
x
x
(PwrL RideThru t)
x
x
<1110>
x
x
x
VG5 Installation & Quick-Start Manual
Parameter Access Level
V/f
Open
Flux
V/f
w/
Loop
Vector
PG
Vector
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
A
A
A
A
A
A
A
A
A
A
A
A
User
Setting