Ablerex TAURUS 10 kVA Installation And Operation Manual page 48

Taurus series 10-80 kva ups
Table of Contents

Advertisement

3.4.2 Cold Start
(1) User can start-up UPS by battery when main input power is not available.
(2) Select
(3) Select Normal mode to start UPS.
3.4.3 Shutdown
(1) Select
3.4.4 Switch to bypass
(1) Select
display.
(2) The Inverter will be shutdown and bypass will supply the power to the load. If the
battery is disconnected, Rectifier and Charger will be shutdown as well.
3.4.5 Switch from normal mode to maintenance bypass
(1) Select
LCD display.
(2)
The Inverter will be shutd
(3) Open the Main Input and Battery Switches
(4) Close the maintenance bypass switch
(5) Open Output and Bypass switch
(6) Wait at least for 10min
3.4.6 Maintenance bypass → normal mode
(1) Close Output, Mains Input and Bypassswitches
Select
(2)
display.
(3) Open maintenance bypass switch
(4) Select
(5) Return to Mimic Display. Wait for few minutes, the rectifier will be start and the
icon
the batteries.
→Command→Operation→Cold start precharge ready on LCD display.
→Command→Operation→Shutdown on LCD display.
→Command→Operation→Shutdownconverter except bypass on LCD
→Command→Operation→Shutdown converter except bypass
own and bypass will supply the power to the load
→Command→Operation→Shutdown converter except bypasson LCD
→Command→Operation→Normal mode on LCD display.
will show you when can close the Batteryline switch/fuses to connect
46
on
192321262008007