Ablerex TAURUS 10 kVA Installation And Operation Manual page 28

Taurus series 10-80 kva ups
Table of Contents

Advertisement

 Maximum Current
Input/Output
Output Power
Voltage
10kVA/10kW
20kVA/20kW
30kVA/30kW
380 V
40kVA/40kW
60kVA/60kW
80kVA/80kW
10kVA/10kW
20kVA/20kW
30kVA/30kW
400 V
40kVA/40kW
60kVA/60kW
80kVA/80kW
10kVA/10kW
20kVA/20kW
30kVA/30kW
415 V
40kVA/40kW
60kVA/60kW
80kVA/80kW
(1)
The UPS is operating at rated voltage, rated power and batteries are charging but regardless of the
overload.
(2)
The UPS is operating at rated voltage and rated power but regardless of the overload.
(3)
12Vbattery blocks × 32pcs. The UPS is operating at rated voltage and rated power but regardless of
the overload.
 Recommended Size of Cables
Mains Input
Capacity
R/S/T/N
2
10kVA
5 mm
2
20kVA
8 mm
2
30kVA
16 mm
2
40kVA
25 mm
2
60kVA
40mm
2
80kVA
50mm
(1)
The recommended maximum length of cabling is less than 10meters.
(2)
Please over size neutral line N by 1.7 times of the phase line for non-linear loads.
Maximum
Input
(1)
Current
19 A
38 A
57 A
75 A
113 A
150 A
18 A
36 A
54 A
72 A
108 A
144 A
17 A
35 A
52 A
69 A
104 A
138 A
(1)
Output/Bypass Input
(2)
PE
R/S/T/N
2
2
3 mm
5 mm
2
2
5 mm
6 mm
2
2
8 mm
13 mm
2
2
10 mm
20 mm
2
2
16 mm
35 mm
2
2
20 mm
40 mm
26
Max.
Max. Battery
Output/Bypass
Discharge
(2)
Input Current
Current
15 A
30 A
46 A
103 A
61 A
137 A
91 A
206 A
122 A
274 A
14 A
29 A
43 A
103 A
58 A
137 A
87 A
206 A
116 A
274 A
14 A
28 A
42 A
103 A
56 A
137 A
83 A
206 A
112 A
274 A
(1)
External Battery
PE
+/-/N
2
2
3 mm
8 mm
2
2
5 mm
16 mm
2
2
8 mm
30 mm
2
2
10 mm
50 mm
2
2
16 mm
70 mm
2
2
20 mm
100 mm
(3)
35 A
69 A
35 A
69 A
35 A
69 A
(1)
PE
2
3 mm
2
8 mm
2
10 mm
2
16 mm
2
25 mm
2
32 mm
192321262008007