Ablerex TAURUS 10 kVA Installation And Operation Manual page 29

Taurus series 10-80 kva ups
Table of Contents

Advertisement

 Recommended Circuit Breaker Size
Input/Output
Voltage
380 V
400 V
415 V
(1)
The sizing takes into account 150% overload capacity.
Output Power
Mains Input
10kVA/10kW
20kVA/20kW
30kVA/30kW
40kVA/40kW
60kVA/60kW
80kVA/80kW
10kVA/10kW
20kVA/20kW
30kVA/30kW
40kVA/40kW
60kVA/60kW
80kVA/80kW
10kVA/10kW
20kVA/20kW
30kVA/30kW
40kVA/40kW
60kVA/60kW
80kVA/80kW
27
(1)
Output/Bypass Input
30 A
65 A
95 A
125 A
185 A
250 A
30 A
60 A
90 A
120 A
175 A
240 A
30 A
55 A
85 A
115 A
170 A
230 A
(1)
25 A
50 A
80 A
105 A
160 A
210 A
25 A
50 A
75 A
100 A
150 A
200 A
25 A
50 A
70 A
95 A
145 A
190 A
192321262008007