Case And Ambient Conditions; Approval/Approval Marks - JUMO mTRON T Operating Manual

Measuring, control, and automation system analog output module 4-channel
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

8 Appendix
8.1.3

Case and ambient conditions

Case type
Dimensions (W × H × D)
Weight
Protection type
Ambient temperature range
Storage temperature range
Resistance to climatic conditions
Site altitude
Mechanical ambient conditions
1
Test conditions are listed in the System Description B 705000.8.
8.1.4

Approval/approval marks

Approval mark
Testing agency
c UL us
Underwriters Laborato-
ries
DNV GL
DNV GL
44
Plastic case for DIN rail mounting in the control cabinet (indoor use);
DIN rail acc. to DIN EN 60715, 35 mm x 7.5 mm x 1 mm
22.5 mm × 103.6 mm × 101.5 mm (without connection elements)
Approx. 140 g
IP 20, according to DIN EN 60529
-20 to +55 °C
-40 to +70 °C
Relative humidity ≤ 90 % annual average without condensation (cli-
matic class 3K3 acc. to DIN EN 60721-3-3 with extended tempera-
ture and humidity range)
Up to 2000 m above sea level
1
Classification acc. to DIN EN 60721-3-3, table 6, class 3M2
Certificate/certifica-
tion number
E201387
TAA000016N
Inspection basis
UL 61010-1 (3. Ed.),
CAN/CSA-22.2
No. 61010-1 (3. Ed.)
Class Guideline
DNVGL-CG-0339
Valid for
all types
all types;
a power supply unit
with DNV GL or GL
type approval is
required (e.g. type
705090)

Advertisement

Table of Contents
loading