NOTE!
The parameters described in this section can be configured either with the setup program or
on the multifunction panel.
6.1
Analog outputs
The four analog outputs can be configured as current or voltage outputs (standard signal) and
are freely scalable.
The analog outputs are exclusively driven by external inputs (NV_AO01 to NV_AO04).
Chapter 6.2 "NV connecting list", page 36
Setup dialog
Parameters
Parameters
Signal type
Zero point
?
End value
?
Selection/settings
Physical output signal
0 to 10 V
2 to 10 V
0 to 20 mA
4 to 20 mA
-1999 to 0 to +9999
-1999 to 100 to +9999
6 Configuration
Description
Standard signal for voltage
Standard signal for voltage
Standard signal for current
Standard signal for current
Scaling start
Scaling end
33