4.3

Connection diagram

CAUTION!
At maximum load, the temperature may exceed 60 °C at the terminals.
As a result the insulation of the cable may be damaged.
The cable must be heat resistant up to at least 80 °C.
4.3.1

Display and connection elements

4.3.2

Analog outputs

Connection
Analog output
DC 0(2) to 10 V or
DC 0(4) to 20 mA
(configurable)
(9)
(8)
(7)
(6)
(5)
(4)
(1) Status displays (LED):
P = Voltage supply
S = Status
(2) Voltage supply Out, DC 24 V
(3) Side system bus Out
(4) Analog output 4
(5) Side system bus In
(6) Analog output 3
(7) Analog output 2
(8) Voltage supply In, DC 24 V
(9) Analog output 1
Output
Terminals
1
1 and 2
2
3 and 4
3
5 and 6
4
7 and 8
4 Electrical connection
(1)
(2)
(3)
Symbol and terminal designation
+
U ,
I x
x
-
1, 3, 5, 7
2, 4, 6, 8