Appendix; Technical Data; Analog Outputs; Electrical Data - JUMO mTRON T Operating Manual

Measuring, control, and automation system analog output module 4-channel
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

8.1

Technical data

8.1.1

Analog outputs

4 analog outputs (configurable)
Voltage DC 0(2) to 10 V
Current DC 0(4) to 20 mA
Selectable output behavior in case of an error acc. to NAMUR recommendation NE 43 (for sig-
nal type 2 to 10 V and 4 to 20 mA).
8.1.2

Electrical data

Voltage supply
Connection
Voltage
Residual ripple
Current consumption
Power consumption
Outputs (terminals 1 to 8)
Connection
Conductor cross section on terminals 1 to 8
Wire or strand without ferrule
Strand with ferrule
Stripping length on terminals 1 to 8
Electrical safety
Electromagnetic compatibility
Interference emission
Interference immunity
Load resistance R
load
≥ 500 Ω
≤ 500 Ω
Lateral (feed via base unit or router module)
DC 24 V +25/-20 %
5 %
240 mA (at DC 19.2 V)
4.8 W
At the front (removable terminal strips with Push-In technology)
2
Min. 0.14 mm
, max. 1.5 mm
Without plastic collar: min. 0.25 mm
With plastic collar: min. 0.25 mm
9 mm
According to DIN EN 61010-1
Overvoltage category III, pollution degree 2
Acc. to DIN EN 61326-1
Class A - only for industrial use -
Industrial requirement
Accuracy
< 0.1 %
< 0.1 %
2
2
, max. 1.5 mm
2
, max. 0.5 mm

8 Appendix

Ambient temperature
influence
± 150 ppm/K
± 150 ppm/K
2
2
43