2.6.5.3 Measurement Type: Density (cont.)
Display
Trim 20
xxxx
14
Loop Tst
xx.x mA
15
Capture
4.00 mA
16
Capture
20.00 mA
17
New Pass
xxx
18
Language
(select)
19
E3 ModHT
Ver 1.0
2
DispFact
(select)
21
History
(current status)
22
Run Time
xxxx.x h
23
History
Reset
24
MeasType
(select)
25
Model
(select)
26
SpringSG
(select)
27
SprgRate
x.x
28
SprgMatl
29
TempLimt
xxx F
3
Length
xx.xx lu
31
Diameter
x.xxx in
32
Weight
x.xx oz
33
CalSelct
(select)
34
Factory
Cal Menu
35a
48-635 E3 Modulevel
®
Displacer Level Transmitter
Action
Fine tune 20 mA point
Enter a mA output value
to test loop
Pressing
in Data Entry
Mode captures current sg
output as 4.00 mA Set Point
In Data Entry Mode, can
adjust loop value to corre-
spond to current sg output
for setting 20.00 mA Set
Point
Enter new password (0 – 255) Displays encrypted value of present password
Select from English, Spanish,
French, German
Transmitter Display
Select "Yes" to display factory
parameter menu as below
Diagnostic Display to view
present status and recent
exceptions
Diagnostic Display showing
elapsed time since power on
or History Reset
Factory only
Factory set
Factory set
Factory set
Factory set
Factory set
Factory set
Factory set
Factory set
Factory set
Select Factory or User
Calibration
Press
to display the
Factory Calibration sub-menu
Comment
Adjust setting (Trim 4 value – 4095) to output exactly 20.0 mA
Current SpecGrav set as 4 mA point. Submerge displacer in
lowest SG liquid. Press
4 mA density.
(8.00 ≤ loop value ≤ 20.00 mA)
Set second SpecGrav point between 8.00 mA and 20.00 mA.
Submerge displacer in higher SG liquid. Press
"capture" this SG as your upper loop value between 8.00 and
20.00 mA.
Default value = 0
Language choice for LCD display
Product identification
Firmware version
Selecting "No" takes you back to beginning of menu
Press
to view recent exceptions, up to ten events
Level, IfcLevel, or Density
E3A, E3B, E3C, E3D, E3E, E3F
Model specific
Model specific
Model specific
Model specific—maximum process temperature for which unit is
suitable
Model specific—length of measuring range
Model specific—outside diameter of displacer
Model specific—weight of displacer and stem assembly
Selects Calibration Parameters used to calculate the
measured PV
CalSelct = Factory
Submenu on page 24
and
to "capture" this SG as your
and
to
23
Need help?
Do you have a question about the E3A Modulevel and is the answer not in the manual?
Questions and answers