DS41
2.6.2

Electrical Connections for JBOX

The connection and wiring procedure for JBOX is described as follows:
1) Open the junction box by unscrewing the 4 cover screws.
2) Pass all System cables through the glands in the junction box housing.
3) To connect the power and input/output signals:
• Prepare the individual wires of the system cables by stripping the
insulation back approximately 11 mm.
• Using a device such as a screwdriver, push down on the orange lever
directly above the clamp (see Figure 2.8).
• Insert the wire into the clamp and release the lever.
The wire will now be held in the spring clamp.
Figure 2.8 - System cable connections to the junction box
The wiring used can be solid or stranded but must meet the following
specifications.
Positions 1-4:
Positions 5-39:
The junction box pinouts are indicated in the following table:
2.8 - Installation
24 - 16 AWG
26 - 20 AWG
DATALOGIC
0.2 - 1.5 mm²
0.14 - 0.5 mm²