5.3.2. Water

Water temperature must not exceed 43°C.
A minimum of 1.4 bar (dynamic pressure on injector) of water pressure is required for the
regeneration valve to operate effectively.
Mandatory
Do not exceed a maximum of 8.6 bar inlet pressure. Should this happen or be subject to
happen, it is necessary to install a pressure regulator upstream the system.

5.3.3. Electrical

There are no user-serviceable parts in the AC/DC adapter, motor, or controller. In the event of a
failure, these should be replaced.
All electrical connections must be completed according to local codes.
Use only the power AC/DC adapter that is supplied.
Mandatory
The use of any other power adapter than the one supplied void the warranty of all electronic
parts of the valve.
The power outlet must be grounded.
To disconnect power, unplug the AC/DC adapter from its power source.
An uninterrupted current supply is required. Please make sure that the voltage supply is
compatible with the unit before installation.
Make sure the controller power source is plugged in.
If the electrical cable is damaged, it must imperatively be replaced by qualified personnel.

5.3.4. Mechanical

Do not use petroleum-based lubricants such as vaseline, oils, or hydrocarbon-based lubricants.
Use only 100% silicone lubricants.
All plastic connections should be hand tightened. PTFE (plumber's tape) may be used on
connections that do not use an O-ring seal. Do not use pliers or pipe wrenches.
Existing plumbing should be in a good shape and free from limescale. In case of doubt, it is
preferable to replace it.
All plumbing must be completed according to local codes and installed without tension or
bending stresses.
Soldering near the drain line should be done before connecting the drain line to the valve.
Excessive heat will cause interior damage to the valve.
Do not use lead-based solder for sweat solder connections.
The distribution tube should be cut flush with the top of the tank. Slightly bevel the ridge in order
to avoid deterioration of the seal whilst fitting the valve.
The drain line must be a minimum of 12.7 mm (½") in diameter. Use 19 mm (¾") pipe if the
backwash flow rate is greater than 26.5 lpm (7 gpm) or the pipe length is greater than 6 m 
(19 ft 8 in).
Do not support the weight of the system on the valve fittings, plumbing, or the bypass.
Ref. MKT-IM-004 / A - 27.10.2016
Installer Manual Fleck 9100 - SXT - Installation
33 / 94