2. PROGRAMMING OUTPUTS (MOD AND RELAY) WITH NO RESET
PROGRAM
MOD 1
ACTION
Fig. 63. Program - Action.
MENU
PROGRAM
MOD 1
ACTION
HEAT
COOL
REV ACT
DIR ACT
HUMID
DEHUMID
SELECT
ACTION
FOR
MOD 1
M24583
T775U SERIES 2000 CONTROLLER
2.1.6. ACTION
1. From the menu, use the
light ACTION.
Default: HEAT
2. Press the
button to display the action selections.
3. Use the
and
value.
4. Press the
button to accept the highlighted selec-
tion and display the next option.
2.2. Program Next Output
For the next output, select the desired MOD or Relay from
the Program menu (see Fig. 57 on page 25).
Go to "2.1.2. SETPOINT" on page 25 to continue
programming.
When you finish programming the outputs, continue with
"1.3. Exit Programming without Reset".
1.3. Exit Programming without Reset
Press the HOME button to leave programming mode and
return to the home screen.
This completes the programming procedure for
controllers that do not use Reset.
27
and
buttons to high-
buttons to select the desired
(Modulating Output or Relay)
62-0255–05