T775U SERIES 2000 CONTROLLER
C
S
SENSOR A
V
1
T
SENSOR B
T
THE T775U WILL ONLY ACCEPT 0-10 VDC AND 4-20 MA SENSORS.
1
IF REPLACING AN H775 CONTROLLER THAT USES A C7600B OR OTHER
2-10 VDC SENSOR, THE SENSOR MUST BE REPLACED. REPLACE THE
C7600B2008 SENSOR (2-10VDC OUTPUT) WITH THE H7655A1001
(0-10 VDC OUTPUT) SENSOR. THE H7655A1001 SENSOR USES THE SAME
ENCLOSURE STYLING AND WIRING AS THE C7600B.
Fig. 5. Sensor Wiring — 3-wire shielded cable
connection from Sensor A to 0-10 Vdc sensor
(H76xx humidity sensor shown).
C
S
SENSOR A
V
T
SENSOR B
T
3. THE T775 HAS AN INTEGRAL LOAD OF 500 OHMS, WHICH RESULTS IN A
10V DROP AT 20MA. TO USE LOOP POWERED WIRING, THE SENSOR MUST
BE CAPABLE OF OPERATION WITH 8V OR LESS ACROSS ITS TERMINAL.
Fig. 6. Sensor Wiring — 2-wire shielded cable
connection from 4-20 mA sensor to
T775 controller (loop powered wiring).
62-0255–05
SHIELDED CABLE
NOTES:
1. SHIELDED CABLE MUST BE
CONNECTED TO A SEPARATE
EARTH GROUND. HOWEVER,
DO NOT GROUND SHIELDED
CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION
FROM SHIELDED CABLE AS
CLOSE AS POSSIBLE TO
SENSOR BODY.
S
C
V
EXAMPLE OF
H76XX HUMIDITY
SENSOR;
0-10 VDC
CONNECTION
M24550
SHIELDED CABLE
NOTES:
1. SHIELDED CABLE MUST BE
CONNECTED TO A SEPARATE
EARTH GROUND. HOWEVER,
DO NOT GROUND SHIELDED
CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION
FROM SHIELDED CABLE AS
CLOSE AS POSSIBLE TO
SENSOR BODY.
S
V
M24890A
C
S
SENSOR A
V
T
SENSOR B
T
Fig. 7. Sensor Wiring — 2-wire shielded cable
connection from Sensor A to a 0-10 Vdc sensor
using separate transformer.
EXAMPLE OF P7640A 4-20 MA SENSOR CONNECTION
PWR
OUT
COM
SHIELDED CABLE
C
S
SENSOR A
V
T
SENSOR B
T
Fig. 8. Sensor Wiring — 2-wire 4-20mA sensor input
to T775 controller using a separate (Vdc only)
transformer.
6
SHIELDED CABLE
NOTES:
1. SHIELDED CABLE MUST BE
CONNECTED TO A SEPARATE
EARTH GROUND. HOWEVER,
DO NOT GROUND SHIELDED
CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION
FROM SHIELDED CABLE AS
CLOSE AS POSSIBLE TO
SENSOR BODY.
S
EXAMPLE OF
P7640A
PRESSURE
SENSOR;
0-10 VDC
CONNECTION
L1
(HOT)
24 VAC
L2
ZERO
12-30 VDC
POWER SUPPLY
S
+
C
NOTES:
1. SHIELDED CABLE MUST BE
CONNECTED TO A SEPARATE
EARTH GROUND. HOWEVER,
DO NOT GROUND SHIELDED
CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION
FROM SHIELDED CABLE AS
CLOSE AS POSSIBLE TO
SENSOR BODY.