Derivative; Schedule - Honeywell T775U2006 Installation Instructions Manual

T775u series 2000
Table of Contents

Advertisement

1. SETUP
NOTES: (Integral Timing)
1. The Integral time is factory set for 400 seconds. This
is a good middle range and should satisfy many
applications. The integral time can be increased for
applications where sensed response is slow, and can
be decreased for applications where sensed
response is fast (e.g. discharge air control).
2. As a starting point, an optimal integral time for
discharge air typically ranges from 12 to 200
seconds. An optimal integral time for room control
typically ranges from 60 to 2,500 seconds. The
purpose of integral action is to reduce or eliminate
SETUP
OUTPUTS
MOD 1
DERIVATIV
Fig. 40. Setup - Outputs - Mod Out - Derivative.
SETUP
OUTPUTS
MOD 1

SCHEDULE

Fig. 41. Setup - Outputs - Mod Out - Schedule.
SETUP
OUTPUTS
MOD 1
DERIVATIV
0
SEC
ENTER

DERIVATIVE

TIME FOR
MOD 1
M24603
SETUP
OUTPUTS
MOD 1
SCHEDULE
YES
NO
USE
SCHEDULE
FOR
OUTPUTS
M24604
T775U SERIES 2000 CONTROLLER
the offset from setpoint during steady state control
that is often seen in proportional only control.
3. Keep in mind that control is most sensitive to
throttling range. Adjust the throttling range first
before any adjustment to integral time. Adjust
throttling range to be as wide as possible to start
since this will provide the most stable control.
Remember that the integral will eliminate the steady
state error so you do not need to have a small
throttling range to have accurate control. (Integral
action allows for controlling to a setpoint even with a
wide throttling range).
1.3.1.4. DERIVATIVE
The Derivative default value is factory set to zero (no
derivative control). It is strongly recommended that the
derivative remain at zero (0) unless you have a very good
reason to adjust it. Derivative control is not needed in the
vast majority of HVAC applications.
1. From the Mod menu, use the
highlight DERIVATIV.
2. Press the
button to display the Derivative sec-
onds.
3. Use the
and
value.
Default: 0 (zero)
Range: 0 to 3,600 seconds
4. Press the
button to accept the seconds and
return to the Mod menu.
1.3.1.5. SCHEDULE
The Schedule option displays only if the USE SCHED
parameter is set to Yes (see page 21).
1. From the Mod menu, use the
highlight SCHEDULE.
2. Use the
and
Default: YES
3. Press the
button to accept the selection and
return to the Mod menu.
Each output can be set up to follow or ignore the built in
scheduler. To disable the scheduler for all outputs, see
"1.3.3.1. USE SCHED" on page 21.
19
and
buttons to
buttons to increase/decrease the
and
buttons to
buttons to highlight YES or NO.
62-0255–05