Min Off Or Min On; Di Options (Digital Input Options) - Honeywell T775U2006 Installation Instructions Manual

T775u series 2000
Table of Contents

Advertisement

T775U SERIES 2000 CONTROLLER
SETUP
OUTPUTS
OPTIONS
MIN OFF
OR
MIN ON
Fig. 48. Setup - Outputs - Options - Min Off/On Time.
SETUP
OUTPUTS
OPTIONS
DI OPTS
Fig. 49. Setup - Outputs - Options - DI Options.
62-0255–05
SETUP
SETUP
OUTPUTS
OUTPUTS
OPTIONS
OPTIONS
MIN OFF
MIN ON
0
SEC
ENTER
ENTER
MINIMUM
MINIMUM
OFF TIME
ON TIME
FOR RELAYS
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
DI OPTS
DISABLE
SETPOINT
SETBACK
ENABLE
IGNORE
SELECT DI
OPTIONS
FOR
OUTPUTS
1.3.3.2. MIN OFF
This is the minimum number of seconds of "off time" or
"on time" for all relays.
1. Press the
2. Use the
desired number of seconds from 0 to 990 seconds
0
SEC
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the
display the DI OPTIONS.
M24610A
NOTES:
1.
2.
3.

1.3.3.3. DI OPTIONS (digital input options)

The DI Option you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.
1. Press the
tions.
2. Use the
SETBACK, or IGNORE.
Default: DISABLE
3. Press the
M24611A
the SHOW RT option.
When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setback, or Ignore):
• DISABLE disables the outputs; relays return to de-
energized state and Mod outputs return to 0% output.
• SETPOINT forces the control to the setpoint
temperature.
• SETBACK enables a setback temperature value to be
programmed for each output.
— To program the Setback temperature with Reset,
see Fig. 73 on page 31.
— To program the Setback temperature without
Reset, see Fig. 60 on page 26.
• ENABLE energizes all relays to 100%. Use this option
carefully.
• IGNORE causes the digital input to have no effect on
the Relay or Mod outputs.
22
MIN ON
or
button to display the Min Off/On value.
and
buttons to increase/decrease the
button to accept the seconds and
The minimum off time applies to all relay
outputs.
When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.
If the minimum off time is not equal to zero
(0), the minimum off time activates at power-
up. To manually override, press the
at any time.
button to display the DI Option selec-
and
buttons to highlight DISABLE,
button to accept the value and display
1. SETUP
button