Method Example - Analog Trim

The Druck DPI 620 Genii can perform an analogue trim on
the 4 to 20 mA loop without connecting to any external
reference meters.
1. Navigate to the calibration folder
2. Select Trim analog method.
3. Follow the on-screen instructions. If channel 2 is set to
Measure Current (24V), this can be used to supply the
reference meter value.