1.2.2.1. Keys Example

Here's an example to try:
When you switch on a factory fresh meter, it starts at the "RMS" page, circled "1" in the
diagram below. This will be our "Home Page".
From here, to now go to the VAh Energy Page, circled
1. Start at "RMS"
2. Go Down
to "Integ" and
3. Go Right
to "VAh"
There are no complicated key sequences, since the grouping of parameters is intuitive. And
the keys always do what they say, under all modes.
A complete
Keypad Operations Map
Main Menu, along with "Clear" and "Set", not shown above, but evident in the left-most
"Main Menu" ("RUN", "CLR", "SET") column. Getting into the Main Menu requires you to
first enter a code.

1.3. EPM 2000 Technical Specs

The EPM 2000 is a high-accuracy, low cost, ultra-compact, power and energy meter that
offers ISO 9000 quality, accuracy, functional flexibility and MODBUS RTU
communications capability. The standard unit flush-mounts in a DIN 96 cutout. Conforms
to UL and CE safety requirements.
The EPM 2000 is designed for retrofit application such as replacement of existing analog
meters and is also usable as a stand-alone meter in custom panels, PDUs, switchboards,
switchgear, UPS's, generator sets, MCCs systems etc.
The EPM 2000 provides easy communication to PLCs, DCS, BMS and other systems
through the use of Modbus RTU communications on RS 485, isolated to 2kV for 1
minute, from other circuits.
The EPM 2000 Series of products are configurable & programmable through the front
panel.

1.3.1. Main Features

The EPM 2000 Series supports the following features:
Measures true RMS electrical parameters. 1 Second updation.
IEC 61036 class 1.0 accuracy.
Provides surge Impulse withstand to IEEE C37.90.1 Surge: 6kV IEC 60060 1.2µS/50µS.
Fast Transient: >4kV IEC 61000-4-4 Level 4, ESD IEC 61000-4-2, Emission meets
CISPR 22
Power 4 Quadrant, Energy 2 Quadrant. Provides 3D power computation for kVA
load bar graph for the quick estimation of consumption from a distance without touching
any keys.
Customized new display for easy readability.
GE Multilin