Plug Load Applications (WA100-PM)
Wiring for Combination Plug Load (Aux Relay with Input
Control Signal) and On/Off Light
In the wiring diagram below, the WA100-PM is used to
control both an On/Off light and a plug load circuit.
WHITE Neutral
BLACK Hot 120-277VAC
Line Voltage
Wires
RED
Switched
Load
120-277VAC
Hot
Ballast
or LED Driver
Neutral
(non-dimming)
Neutral
Plug Load
Call 1 888 694 3533
GE is a trademark of the General Electric Company. All other trademarks are the property of their respective owners.
Information provided is subject to change without notice. All values are design or typical values when measured
under laboratory conditions. Current and GE Lighting are businesses of the General Electric Company. © 2017 GE
Neut
Load
www.daintree.net
Wireless Adapter with Power Monitoring
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
15A+45mA
Hot
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY
UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
00228103007-00000
IEEE Address:
Hot
RED
SW Hot
RED
Aux Relay with input
control signal (20A)
products.currentbyge.com
Driver: On/Off
Plug Load: On/Off
Perform Installation Test Suite 1
Blue (Digital In 1)
15A
Yellow (Digital In 2)
Red
Relay
Orange (0-10V In)
45mA
Red (24VDC Output)
White
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Black
Gray (Ground)
WA100-PM
CONTAINS FCC ID: Z6G-DT357
CONTAINS IC: 10478A-DT357
RoHS
C
US
CAN ICES-3 (B)/NMB-3(B)
Hot
**
BLUE Control Output
BLACK Common
RED 24VDC
GREEN
Ground
DIP Switches
Wired
OFF
DIP Switch Positions:
Sensor:
O
1 2 3 4 5 6
N
None
( # 2, 4 ON)
Low Voltage
Wires
Cap unused
wires.
RED 24VDC Power
GREEN Digital Ouptut LSD
*0-10V Dimming output , 5 mA available, Up to
10 LED drivers or fluorescent ballasts typical; the
chance of noise on the signal increases with more.
**Relays used to control plug loads must be
compliant with UL498 (Attachment Plug and
Receptacles) or equivalant .