Plug Load Applications (WA100-PM)

ii. Appendix 1: Installation Advisory - Plug Load Applications (WA100-PM)
Plug load control functionality for the WA100-PM is made available with WA100-PM firmware provided in ControlScope
Manager version 3.5.3.1. During testing the Plug Load cycles on/off in sync with the lighting load. Relays used to control
plug loads must be compliant with UL498 (Attachment Plug and Receptacles) or equivalent.
Wiring for Combination Plug Load (Basic Aux Relay) and Dimming Light
In the wiring diagram below, the WA100-PM is used to control both a
dimming light and a plug load circuit.
BLACK Hot 120-277VAC
Line Voltage
Wires
RED
Switched
Load
120-277VAC
Hot
Dimming Ballast
or LED Driver
Neutral
(0-10VDC)
Neutral
Plug Load
Wiring for Combination Plug Load (Basic Aux Relay) and On/Off Light
In the wiring diagram below, the WA100-PM is used to control both an
On/Off light and a plug load circuit.
BLACK Hot 120-277VAC
Line Voltage
Wires
RED
Switched
Load
120-277VAC
Hot
Ballast
or LED Driver
Neutral
(non-dimming)
Neutral
Plug Load
*0-10V Dimming output , 5 mA available, Up to 10 LED drivers or fluorescent
ballasts typical; the chance of noise on the signal increases with more.
**Relays used to control plug loads must be compliant with UL498
(Attachment Plug and Receptacles) or equivalant .
WHITE Neutral
Neut
Load
www.daintree.net
Wireless Adapter with Power Monitoring
45mA
Model: WA100-PM
White
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
15A+45mA
Hot
Ambient Temperature -4° to 149°F (-20° to 65°C)
Black
FOR INDOOR USE ONLY
UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
00228103007-00000
IEEE Address:
C
GRAY (-) Analog Ground
VIOLET (+) 0-10V Analog Output (dimming control)
Hot
WHITE Neutral
Neut
Load
www.daintree.net
Wireless Adapter with Power Monitoring
45mA
Model: WA100-PM
White
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
15A+45mA
Hot
Ambient Temperature -4° to 149°F (-20° to 65°C)
Black
FOR INDOOR USE ONLY
UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
00228103007-00000
IEEE Address:
C
Hot
Driver: On/Off +
0-10V dimming
Plug Load: On/Off
Perform Installation Test Suite 1
Blue (Digital In 1)
15A
Yellow (Digital In 2)
Red
Relay
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
WA100-PM
Gray (Ground)
CONTAINS FCC ID: Z6G-DT357
RoHS
CONTAINS IC: 10478A-DT357
US
CAN ICES-3 (B)/NMB-3(B)
*
Hot
+24VDC
Aux.
Relay
(20A)
Driver: On/Off
Plug Load: On/Off
Perform Installation Test Suite 1
Blue (Digital In 1)
15A
Yellow (Digital In 2)
Red
Relay
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Gray (Ground)
WA100-PM
CONTAINS FCC ID: Z6G-DT357
RoHS
CONTAINS IC: 10478A-DT357
US
CAN ICES-3 (B)/NMB-3(B)
Hot
+24VDC
Aux.
Relay
(20A)
DIP Switches
Wired
DIP Switch Positions:
Sensor:
O
1 2 3 4 5 6
N
None
(# 2, 3 ON )
Low Voltage
Wires
Cap unused
wires.
**
RED 24VDC Power
GREEN Digital Ouptut LSD
GND
DIP Switches
Wired
DIP Switch Positions:
Sensor:
O
N
1 2 3 4 5 6
None
(# 2, 4 ON )
Low Voltage
Wires
Cap unused
wires.
**
RED 24VDC Power
GREEN Digital Ouptut LSD
GND
1
OFF
ON
OFF
ON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents