Fig. 16: Bypass WA100 switched power and 0-10V dimming control during power failure
In the wiring diagram here, while Regular power is supplied to the LVS model RRU-X-UM the WA100-PM provides
switched On/Off power and 0-10V dimming control to the fixture driver or ballast .
When the RRU-X-UM senses loss of Regular power it passes Emergency power directly to the fixture.
It disconnects the WA100-PM switched output and disconnects the WA100-PM dimming control so that the fixture will
operate at maximum output during the power failure.
EMERGENCY
Line Voltage (120-277VAC)
WHITE Neutral
Hot
Wiring to
bypass WA100
Line Voltage
and Dimming
control to
power failure
REGULAR
Line Voltage
(120-277VAC)
WHITE
Neutral
*
LVS Model RRU-X-UM
Hot
*
Connect
120VAC to BLK
ORG
277VAC to
VIOLET 0-10V
FIXTURE
LED Driver or
Electronic Dimming
Ballast (0-10VDC)
GRAY
VIOLET
0-10V Ground
0-10V
dimming
WHITE Neutral
Control
BLACK Hot
RED Switched Load
120-277VAC
WA100-PM