Trimming And Dressing; Securing Low Voltage Wires; Secure Unused Wires - Current WA100-PM Installation Instructions Manual

Table of Contents

Advertisement

Wireless Adapter (WA100-PM)

Trimming and Dressing

When the wiring connections have been decided and extra (unused) wires identified, secure the unused wires to keep
them neat , out of the way, and protected against shorting or interference with other components, wiring, or devices.
It is best to trim unused wires to about 5 inches in length, isolate them using a wire nut or equivalent , then bundle and
bind them close to the adapter's body. Be sure that unused Red and Violet output wires are completely isolated from all
other wires. Unused line voltage wires must be securely isolated and housed inside a junction box, or other approved
electrical enclosure.

Securing Low Voltage Wires

1. Make sure the unit is NOT powered.
2. Cut the unused low voltage wires approximately five
inches from where they exit the WA100-PM body.
3. Isolate the end of each wire using a wire nut , shrink
tubing, or equivalent .
4. Wrap the unused low voltage wires around the side of
the adapter in a bunch, and secure them in place using a
white or clear cable tie.
Fig. 18: Secure unused wires
Line Voltage
Hot 120/230/277VAC
Wires
BLACK 14AWG
WHITE 18AWG Neutral
J-Box or
RED 14AWG
Equivalent
Switched load
RED: 24VDC power output
Cap unused wires
VIOLET: 0-10V output
Tie Wrap (or equiv.)