Alternate Switching - Current WA100-PM Installation Instructions Manual

Table of Contents

Advertisement

Wireless Adapter (WA100-PM)
Fig. 12: Alternate Switching:
This configuration allows the WA100-PM to alternate in switching separate drivers, providing no load (0%), partial load
(according to the driver loading) or full load (100%).
Always connect the smaller proportion of the total load to the WA100-PM's RED Switched Load wire.
WHITE Neutral
BLACK Hot 120-277VAC
Line Voltage
Wires
RED Switched Load 120-277VAC
Driver/Ballast 1
Neutral
(1% to 49% of
total Load)
Driver/Ballast 2
Neutral
(50% to 99% of
total Load)
15A
Load
Wireless Adapter with Power Monitoring
45mA
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
15A+45mA
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY
UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
00228103007-00000
IEEE Address:
C
Hot
Hot
Driver:

Alternate Switching

Alternate Switching States
Intensity Level
Off (0%)
Low (1-49%)
Medium (50-99%)
Maximum (100%)
Blue (Digital In 1)
Yellow (Digital In 2)
Relay
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Gray (Ground)
WA
CONTAINS FCC ID: Z6G-DT357
CONTAINS IC: 10478A-DT357
RoHS
US
CAN ICES-3 (B)/NMB-3(B)
Hot
Aux.
Relay
DIP Switches
Wired
OFF
DIP Switch Positions:
Sensor:
O
N
1 2 3 4 5 6
None
( # 3 O N )
WA100 Switched Aux Relay
Off
Off
On
Off
Off
On
On
On
Low Voltage
RED 24VDC Power
+24VDC
GREEN Digital Ouptut LSD
GND
14
ON
Wires
Cap unused
wires.