Joining The Zigbee Lighting Control Network; Troubleshooting; The Installation Test Procedure Fails; The Red Error Led Is Flashing Once Every Second - Current WA100-PM Installation Instructions Manual

Table of Contents

Advertisement

Wireless Adapter (WA100-PM)

Joining the ZigBee Lighting Control Network

After the Installation Test is complete the WA100-PM is ready to communicate with the Daintree Wireless Area Controller
(WAC) and the Daintree ControlScope Manager (CSM) web-based lighting management user interface. Upon commissioning,
the WA100-PM "Join" LED turns on solid and remains on as long as the WA100-PM is included in the ZigBee Network.
After joining the network, the low voltage devices connected to the WA100-PM do not directly control the lights that are
wired to the same WA100-PM. The control signals from the low voltage devices pass through the WA100-PM and are sent
wirelessly to the ControlScope network. Depending on the zone and device configuration in the CSM, wireless signals from
the WAC to the WA100-PM determine the operation of the light(s).
For more information about configuring the lighting control network, see the instructions and on-line help provided with the
ControlScope Manager application.

Troubleshooting

The Installation Test procedure fails.

1. Confirm that the WA100-PM is powered.
2. Check the connections from the WA100-PM to the driver(s) and low voltage control devices.
3. Check to be sure the WA100-PM DIP switch settings are correct .
4. Press and hold the Reset button for 3 seconds to reset the WA100-PM.
5. Perform the Installation Test again.
Connected lights do not turn Off during the occupancy sensor Installation Test .
1. Make sure the sensor is not detecting occupancy.
2. Check the occupancy sensor time delay and make sure it is set for minimum.
When the ControlScope lighting control network is commissioned, time delays are set in the Daintree
CSM system. These CSM "Off delays" start counting down after the sensor's internal time delay expires.
Therefore, set occupancy sensors for the minimum time delay during the WA100-PM installation.

The red Error LED is flashing once every second.

DIP switch configuration is invalid. At least one DIP switch must be On to enable an interface.
1. Enable the interface(s) that are connected by turning appropriate DIP switch(es) On.
2. Press the blue Reset button for 3 seconds to reset the unit .
26