Current WA100-PM Installation Instructions Manual page 29

Table of Contents

Advertisement

Plug Load Applications (WA100-PM)
Wiring for Combination Plug Load (Aux Relay with
Input Control Signal) and Dimming Light
In the wiring diagram below, the WA100-PM is used to
control both a dimming light and a plug load circuit.
WHITE Neutral
BLACK Hot 120-277VAC
Line Voltage
Wires
RED
Switched
Load
120-277VAC
Hot
Dimming Ballast
or LED Driver
Neutral
(0-10VDC)
Neutral
Plug Load
Neut
Load
www.daintree.net
Wireless Adapter with Power Monitoring
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
15A+45mA
Hot
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY
UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
00228103007-00000
IEEE Address:
Hot
GRAY (-) Analog Ground
VIOLET (+) 0-10V Analog Output (dimming control)
SW Hot
RED
RED
Aux Relay with input
control signal (20A)
Driver: On/Off +
0-10V dimming
Plug Load: On/Off
Perform Installation Test Suite 1
Blue (Digital In 1)
15A
Yellow (Digital In 2)
Red
Relay
Orange (0-10V In)
45mA
Red (24VDC Output)
White
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Black
Gray (Ground)
WA100-PM
CONTAINS FCC ID: Z6G-DT357
RoHS
CONTAINS IC: 10478A-DT357
C
US
CAN ICES-3 (B)/NMB-3(B)
*
Hot
Control Output
**
BLUE
BLACK Common
RED 24VDC
GREEN
Ground
DIP Switches
Wired
OFF
DIP Switch Positions:
Sensor:
O
1 2 3 4 5 6
N
None
(# 2, 3 ON )
Low Voltage
Wires
Cap unused
wires.
RED 24VDC Power
GREEN Digital Ouptut LSD
*0-10V Dimming output , 5 mA available, Up to
10 LED drivers or fluorescent ballasts typical; the
chance of noise on the signal increases with more.
**Relays used to control plug loads must be
compliant with UL498 (Attachment Plug and
Receptacles) or equivalant .