User Guide | Liquid level controller, EKE 347
Setup & service menu - COMMISSIONING
Parameter
Reference
Main switch
Liquid level setpoint
Operation mode
Alarm setup
Lower level limit
Upper level limit
Level alarm mode
Lower delay
Upper delay
Lower level hysteresis
Upper level hysteresis
Function common alarm
Oscillation detect band
Oscillation detect timeout
Force pump OFF in stop mode
IO Lower level limit
IO Upper level limit
IO Lower level hysteresis
IO Upper level hysteresis
IO Lower delay
IO Upper delay
IO Level limit
IO Level delay
IO Level hysteresis
IO Level action
Control
Control Method
Regulating principle
P-band
Integration time Tn
Neutral zone
Difference
Period time for AKV/AKVA
Minimum OD
Maximum OD
Display
Language
Output indication
Login timeout
Backlight timeout
Password daily
Password service
Password commission
IO config
System configuration
Level signal setup
Voltage at low liquid level
Voltage at high liquid level
Current at low liquid level
Current at high liquid level
Valve position setup
Voltage at closed valve position
Voltage at open valve position
Current at closed valve position
Current at open valve position
Common alarm setup
Multiple valve setup
Multiple valve pattern
Valve A capacity
Valve B capacity
Valve C capacity
ICAD takeover OD
IO module setup
Communication
CAN ID
CAN baudrate
Modbus ID
Modbus baudrate
Modbus mode
Modbus mapping
Valve B CAN ID
Valve C CAN ID
IO Mod. CAN ID
© Danfoss | DCS (ADAP-KOOL®) | 2016-04
Options
On, Off
0 - 100%
Master, IO, Slave
0 - 100%
0 - 100%
Time, Hysteresis
0 - 999 sec
0 - 999 sec
0-20 %
0-20 %
Not follow; Follow up; Follow low; Follow all
0 - 100%
2 - 30 min
Yes / No
0 - 100%
0 - 100%
0-20 %
0-20 %
0 - 999 sec
0 - 999 sec
0 - 100%
0 - 999 sec
0-20 %
Falling,Rising
On/Off ,P, PI
Low, High
5 - 200%
60 - 600 sec
0 - 25%
0,5-25%
3-15 sec
0 - 99%
1 - 100%
EN,CN,PT,RU,SP,FR,IT, GER, ARAB
level, OD
1 - 120 min
0 - 120 min
3 -digit, 0 - 999
3 -digit, 0 - 999
3 -digit, 0 - 999
ICAD+NC, ICAD, AKV/A+NC, AKV/A, NC only
AKS 4100, AKS 41, Current, Voltage
0-10V
0-10V
0-20 mA
0-20 mA
Not used, Current, Voltage
0-10V
0-10V
0-20 mA
0-20 mA
D04, High alarm, D03, Disp only
Not used, 2 same cap, 2 dif cap, 3 same cap, 3 dif cap
Parallel,Sequence
0-100 %
0-100 %
0-100 %
0-100%
Used, Not used
1 - 127
20k, 50k, 125k, 250k, 500k, 1M
0 - 120
0, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400
8N1, 8E1, 8N2
Operation, Setup
1 - 127
1 - 127
1 - 127
Default
values
Off
50.0%
Master
15%
85%
Time
10 sec
50 sec
3%
5%
Not follow
100%
20 min
No
5%
95%
3%
3%
10 sec
50 sec
50%
10 sec
3%
Falling
PI
Low
30.0%
400 sec
2.0%
2%
6 sec
0%
100%
EN
Level
10 min
2 min
100
200
300
ICAD + NC
AKS4100
0 V
10 V
4 mA
20 mA
Not used
0 V
10 V
4 mA
20 mA
High alarm
Not used
Parallel
50%
50%
30%
80%
Not used
1
500k
1
19200
8E1
Operation
2
3
4
To be continued......
DKRCI.PD.RP0.A4.02 | 6