Aspirating Smoke Detector
Notice!
FCS-320-TP2 and FCS-320-TT2 variants:
These unit types are factory prepared for the installation of two detector modules:
The fan covers for both aspiration pipes are removed.
The two pipe system connections are cut out.
The pin pair on jumper BR1 is open (see Number of Detector Modules).
5.3

Settings on the Unit Motherboard

X1
HEAD 1
JU4
Figure 5.1: Settings on the motherboard
5.3.1

Setting the Fan Voltage

The standard fan voltage setting is 6.9 V. In critical applications, the fan voltage may be
switched to 9 V. This increases the transport speed in the pipe system, thus achieving faster
detection with longer pipe lengths.
To switch to 9 V, pull out jumper JU1.
Fan voltage
6.9 V
9 V
Bosch Sicherheitssysteme GmbH
Carefully pull the display board connection cable from the motherboard ("DISPLAY"
connection) and remove the housing cover. Once the unit is installed, fix the cover with a
service clip.
Spread the brackets provided for fixing the detector module slightly apart.
Carefully insert the detector module until you hear it click into place. Make sure that the
used detector module is fixed tightly and securely by the bracket by additionally pushing
together the brackets by hand.
Connect detector module 1 to the "HEAD1" connection on the motherboard using the
flatband cable. FCS-320-TP2 and FCS-320-TT2 variants: Connect detector module 2 to the
"HEAD2" connection on the motherboard using the flatband cable.
Reconnect the display board cable to the "DISPLAY" connection on the motherboard.
DIAG
X2
X3
HEAD 2
X4
DISPLAY X5 2 1
JU4
1 2
JU1
1 2
JU1
Installing the Aspirating Smoke Detector | en
Jumper JU1, pin no. 1+2
X
O
Operation Guide
79
2018.04 | 2.0 | F.01U.130.926