Number Of Detector Modules; Installing The Unit - Bosch FCS-320-TP2 Operation Manuals

Fcs-320 series. aspirating smoke detector
Hide thumbs Also See for FCS-320-TP2:
Table of Contents

Advertisement

80
en | Installing the Aspirating Smoke Detector
X = pin pair bypassedO = pin pair open
Caution!
Re-initialize the airflow if you switch the fan voltage. Close or open the jumper JU1 only when
!
the device is switched off.
See also
5.3.2

Number of Detector Modules

The number of populated detector modules is factory set in line with the model variant
(jumper JU4 on the unit's motherboard; see , page 79).
Variant
FCS-320-TP1/FCS-320-TT1
FCS-320-TP2/FCS-320-TT2
X = pin pair bypassed O = pin pair open
5.4

Installing the Unit

Notice!
When selecting the installation location, it must be ensured that the unit displays are easily
visible.
Remember when planning that the unit fans generate a noise level of approx. 45 dB(A).
The installation location may not be in any door opening area.
A
Installation of the FCS-320
The air outlet on the unit must not be obstructed. There must be a free area of 10 cm in front
of the air outlet.
The aspirating smoke detector can be installed with the aspiration device pointing upwards or
downwards. Rotate the cover through 180° in the required direction.
2018.04 | 2.0 | F.01U.130.926
, page 79
, page 79
1
2
≥ 10 cm
Number of detector modules Jumper JU4, pin no. 1+2
1 detector module
2 detector modules
B
≥ 10 cm
Operation Guide
Aspirating Smoke Detector
X
O
A
Aspiration device
upwards
B
Aspiration device
downwards with air
outlet opening upwards
1
Smoke aspiration pipe
2
Air-return pipe
Bosch Sicherheitssysteme GmbH