Fcs-320 Functional Test; Preparations For The Functional Test - Bosch FCS-320-TP2 Operation Manuals

Fcs-320 series. aspirating smoke detector
Hide thumbs Also See for FCS-320-TP2:
Table of Contents

Advertisement

Aspirating Smoke Detector
Check whether...
4
1.
2.
3.
4.
If no faults are detected, the functionality of the FCS-320 and/or the airflow sensor is checked
using the test pipe or diagnostic software.
7.6

FCS-320 Functional Test

Check functionality using the test pipe, a digital pressure gauge and the diagnostic software.
The aspirating smoke detector must be operating for at least 30 min.
7.6.1

Preparations for the Functional Test

Select the following parameter settings using the FSP‑5000‑RPS programming software (the
settings in the bold font indicate deviations from the default setting):
Activation threshold for airflow malfunction
Low (+/- 10% volume flow change)
Average (+/- 20% volume flow change)
High (+/- 30% volume flow change)
Very high (+/- 50% volume flow change)
Airflow fault delay
30 seconds
2 minutes
15 minutes
60 minutes
Connecting the digital pressure gauge:
Bosch Sicherheitssysteme GmbH
All inlet holes are free
The pipe system has breaks or fractures
All pipe connections are tight
The fan can blow out freely
The correct aspiration reducing film sheets were used
Connect the test pipe
Connect the pressure measuring hose to the adapter connection B.
Connect the 4-pin plug of the adapter to the digital pressure gauge and switch it on.
Operation Guide
Commissioning | en 107
Alarm delay
0 seconds
10 seconds
30 seconds
60 seconds
LOGIC·SENS filter
Off
On
2018.04 | 2.0 | F.01U.130.926

Advertisement

Table of Contents
loading

Table of Contents