Setting the detector address

Figure 5.1: Setting the detector address
The Aspiration smoke detector address is set using the 8-pin DIP switches on the PC board
and a suitable sharp object. The default address is 0 (all DIP switches to off).
The DIP switch settings for all approved addresses are listed in the table in the Appendix on
Appendix, page 88 (0= off, 1= on).
Address
(A)
0
1 to 254
255 = CL Automatic address assignment in classic LSN
x = possible, - = not possible
Notice!
It is not permitted to use different operating modes in one loop/stub/T-tap next to each
other.
5.3

Installing the unit

Notice!
When selecting the installation location, ensure that the LEDs are easily visible.
Remember when planning that the unit fans generate a noise level of approx. 40 dB(A).
In order to prevent damage to the device, ensure that the installation location is not in a door
opening area.
The aspirating smoke detector can be installed with the aspiration device pointing upwards or
downwards. Turn the detector module in the cover by 180° as applicable.
Bosch Sicherheitssysteme GmbH
DIP
Operating mode
Automatic address assignment in "improved
version" LSN mode
Manual address assignment in improved version
LSN mode
mode (address range: max. 127)
Operation guide
Installing the Aspiration smoke detector | en
Network structure
Loop
Stub
X
X
X
X
X
X
2020.04 | 5.1 | F.01U.088.878