Smoke detector POPIT base Table of contents | en Table of contents Safety Overview Installation Installing the base Wiring Base POPIT addresses Technical data Wire lengths Bosch Security Systems B.V. 2022.09 | 01 | F.01U.396.537...
Notice! FAH-350-190 high temperature The FAH-350-190 Heat Detector head should not be used with the FAA-350-B6 POPIT base due to a higher temperature threshold from the FAH-350-190 detector head. The temperature range is too high for the electronics in the FAA-350-B6 POPIT base and may not signal an alarm/trouble event.
H2 (in/out) POPEX bus (-) Installation Danger! Install, test, and maintain this device according to these instructions, NFPA 72 standards, local codes, and the Authority Having Jurisdiction (AHJ) in your area. Bosch Security Systems B.V. 2022.09 | 01 | F.01U.396.537...
When using a separate supply, connect the negative side to the control panel ground. Cut, strip, and place the in and out wires for terminal connection as individual ends. Connect the power loop to the control panel’s switched auxiliary power. 2022.09 | 01 | F.01U.396.537 Bosch Security Systems B.V.
Page 7
1 FAA-350-B6 2 Switched auxiliary power 3 POPIT Bus Remote LED Installation 1 Remote LED (DRA-5 2 Black wire (to Terminal shown for 12V installations only) 3 Red wire (to Terminal L2) Bosch Security Systems B.V. 2022.09 | 01 | F.01U.396.537...
Refer to the following table for DIP switch 0 settings and the following address switch table for DIP switch configuration settings for ZONEX and ZONEX2. Control panel DIP switch 0 setting D7212B1 Leave switch 0 ON. D8112 D9112B1 2022.09 | 01 | F.01U.396.537 Bosch Security Systems B.V.
Page 9
Refer to ZONEX and ZONEX 2 B8512G-E point address chart ZONEX 1 and ZONEX 2 point address chart Address Switch ZX 1 ZX 2 B299 x00* x01* x02* x03* x04* x05* x06* x07* x08* Bosch Security Systems B.V. 2022.09 | 01 | F.01U.396.537...
Page 10
| Base POPIT addresses Smoke detector POPIT base Address Switch ZX 1 ZX 2 B299 2022.09 | 01 | F.01U.396.537 Bosch Security Systems B.V.
Page 11
Smoke detector POPIT base Base POPIT addresses | en Address Switch ZX 1 ZX 2 B299 Bosch Security Systems B.V. 2022.09 | 01 | F.01U.396.537...
Page 12
| Base POPIT addresses Smoke detector POPIT base Address Switch ZX 1 ZX 2 B299 2022.09 | 01 | F.01U.396.537 Bosch Security Systems B.V.
Page 13
Smoke detector POPIT base Base POPIT addresses | en Address Switch ZX 1 ZX 2 B299 Bosch Security Systems B.V. 2022.09 | 01 | F.01U.396.537...
Page 14
ZONEX 1: Points 9 to 127 (D9412G); Points 9 to 75 (D7412G). ZONEX2: Points 129 to 247 (D9412G). B299: x = B299 module address 0-5. *These point numbers are not available for B299 address 0 2022.09 | 01 | F.01U.396.537 Bosch Security Systems B.V.