Installing The Aspirating Smoke Detector; General; Installing The Detector Module - Bosch FCS-320-TP2 Operation Manuals

Fcs-320 series. aspirating smoke detector
Hide thumbs Also See for FCS-320-TP2:
Table of Contents

Advertisement

78
en | Installing the Aspirating Smoke Detector
5

Installing the Aspirating Smoke Detector

5.1

General

The regulations, guidelines and provisions described in Regulations apply.
The following must be observed when installing the FCS-320 Aspirating Smoke Detector:
Warning!
Installation must only be performed by authorized and specialized personnel!
!
Switch off the unit before carrying out any connection work!
Do not connect or disconnect the detector module while switched on!
5.2

Installing the Detector Module

Notice!
Only DM-TP-50(80), DM-TP-10(25) and DM-TP-01(05) detector modules certified to VdS may
be used.
The detector module settings are configured via the RPS software. All DIP switches on the
detector module must be set to "OFF".
The sensitivity value is based on measurements with standard test fires (old value in
brackets).The activation threshold for the airflow malfunction is set to 20% volume flow
change by default. Higher values are not permitted within EN 54‑20 or ISO 7240-20.
Installing the Detector Module
Caution!
Electrostatic discharge (ESD)! This can damage electronic
components. Ground yourself using a wrist strap or take other suitable measures.
Proceed as follows to install the detector module:
2018.04 | 2.0 | F.01U.130.926
Do not interfere with, modify or convert the equipment. If adjustments cannot be
avoided, consult with the operator, the unit manufacturer and/or the supply company.
All changes to the house mains (230 V/400 V supply) and to third-party systems must be
executed by the builder. This includes e.g.
Primary connection of the mains charger
Carrying out any potentially essential lightning and surge protection measures in
compliance with relevant standards
1
5
2
Open the unit by carefully unlocking the housing cover's quick locks.
3
4
6
Operation Guide
Aspirating Smoke Detector
HEA D1 DIAG HEA D2 DIS PLA Y
Bosch Sicherheitssysteme GmbH