en | Planning
U-pipe system activation thresholds per pipe system
Activation
Number of openings
thresholds
1 obstructed opening
2 obstructed openings
3 obstructed openings
4 obstructed openings
5 obstructed openings
6 obstructed openings
... will be recognized by the setting level x
— not possible, 0 not practical
Example
If 3 of a total of 10 air sampling openings are found to be obstructed, the switch for setting
the airflow monitoring should be set to level I.
Notice!
When planning in accordance with EN 54‑20 or ISO 7240-20, level I or II must always be set
for airflow monitoring.
M-pipe system - single-hole monitoring
FAS / FCS
1 pipe system
FCS-320-TP1
FCS-320-TT1
2 pipe systems
FCS-320-TP2
FCS-320-TT2
M-pipe system for space protection
Limiting values
Min. distance FCS-320 – last T-fitting
2018.04 | 2.0 | F.01U.130.926
A
B
A
B
FAS / FCS
2
4
III
II
0
III
0
0
0
0
0
0
0
0
d
C
d
C
Operation Guide
Aspirating Smoke Detector
6
8
10
I
II
I
III
II
I
0
III
II
0
0
III
0
0
0
D
D
Bosch Sicherheitssysteme GmbH
12
14
I
II
I
III
II
4 m