Bosch FCS-320-TP2 Operation Manuals page 40

Fcs-320 series. aspirating smoke detector
Hide thumbs Also See for FCS-320-TP2:
Table of Contents

Advertisement

40
en | Planning
General
1.
Selection:
Select the planning table with or without air filter,
as applicable.
Result:
Planning table and specified air filter
2.
Selection:
Select the number of air sampling openings from
the planning table. Note the possible sensitivity
classes.
Result:
Specified detector module with specified setting
and alarm threshold
3.
Selection:
Select the sensitivity (sensitivity class) of the
system according to the gradation described in
Defining the Response Sensitivity.
Result:
Specified sensitivity class in accordance with EN
54‑20
4.
Selection:
Select other pipe components, such as a water
separator and detonation safety barrier.
Result:
Specified planning table
5.
Selection:
Select the possible pipe length for the relevant pipe
shape and fan voltage.
Result:
Specified planning in accordance with EN 54‑20 for
the previously specified parameters
You will find the planning tables in question in Planning without filter and Planning with air
filter.
Abbreviation
DM
S
MA
PA
l [m]
2018.04 | 2.0 | F.01U.130.926
Example
Select the planning table without air filter, Planning
without filter, page 41
In the Planning without filter, page 41 table, select
the column with eight air sampling openings (Number
of air sampling openings, 8)
In the Planning without filter, page 41 table, select
the response sensitivity you require (class A, B or C)
from the column highlighted in red. You must select
the class that corresponds to the installed detector
module and the configured sensitivity.
Select With water separator, page 42 .
In the With water separator, page 42 table, select the
pipe shape and fan voltage you require, and note the
permissible total pipe length.
Meaning
Detector module
Sensitivity (% LT/m)
Main alarm
Pre-alarm
Permissible total pipe length in
meters
Operation Guide
Aspirating Smoke Detector
CTN
DM‑01(05)
DM-TP-01(05)
DM‑10(25)
DM-TP-10(25)
DM‑50(80)
DM-TP-50(80)
Bosch Sicherheitssysteme GmbH

Advertisement

Table of Contents
loading