Simplified Pipe Planning - Bosch FCS-320-TP2 Operation Manuals

Fcs-320 series. aspirating smoke detector
Hide thumbs Also See for FCS-320-TP2:
Table of Contents

Advertisement

Aspirating Smoke Detector
4 obstructed openings
5 obstructed openings
6 obstructed openings
... will be recognized by the setting level x
— not possible, 0 not practical
Example
If 4 of a total of 12 air sampling openings are found to be blocked, the switch for setting the
airflow monitoring should be set to level II.
Notice!
When planning in accordance with EN 54‑20 or ISO 7240-20, level I or II must always be set
for airflow monitoring.
See also
4.8

Simplified Pipe Planning

Simplified planning is used for equipment protection and in premises with smaller
dimensions. The benefit of this type of planning is the standard diameters of the suction
openings.
Planning is to be carried out according to regulations specified in Standard Pipe Planning.
Additionally, the following limiting values and opening diameters must be observed. An
additional accessory (air filter, condensate separator etc.) can have an effect on the maximum
pipe length.
I-pipe system - simplified planning
1 pipe system
FCS-320-TP1
FCS-320-TT1
2 pipe systems
FCS-320-TP2
FCS-320-TT2
I-pipe system, e.g. for equipment protection
Limiting values
Min. distance FCS-320 – 1st air sampling opening
I-pipe system
Max. distance FCS-320 – 1st air sampling opening
Max. distance: 1st air sampling opening – last air sampling opening
Max. overall pipe length (Ø 25 mm)
Min. distance between air sampling openings
Max. distance between air sampling openings
Max. number of air sampling openings (n) per pipe system
Bosch Sicherheitssysteme GmbH
Standard Pipe Planning, page 39
10
9
8
7
6
4 5
3
FAS / FCS
i
1 2
2
10
8 9
7
6
5
4
3
2
i
1
0
0
0
d
d
1
10
8 9
7
5
6
4
3
2
FAS / FCS
1
Operation Guide
III
II
0
III
0
III
2018.04 | 2.0 | F.01U.130.926
Planning | en
55
2 m
20 m
20 m
40 m
0.1 m
4 m
18