112 en | Maintenance
8.2.4

4 Flashes - Error: Air Pressure Correction Voltage Monitoring

In operation with two detector modules, both LEDs flash. When troubleshooting, the following
steps should be carried out in the specified order.
2018.04 | 2.0 | F.01U.130.926
Restore the operating voltage and run the unit for a few minutes.
If the fan connection is faulty, the malfunction will no longer occur.
Check the fan connection on the motherboard: terminal 1 = red, terminal 2 = black).
The fans are faulty or obstructed
If the fan connection is correct (troubleshooting step 2), the malfunction will
reoccur.
Measure the fan voltage (DC) using a multimeter.
If the fan voltage is outside the limits specified below, the fan may be faulty:
If the fan voltage is set at 6.9 V, the maximum permissible setting is 7.6 V and the
minimum is 6.0 V.
If the fan voltage is set at 9.0 V, the maximum permissible setting is 10.0 V and the
minimum is 7.8 V.
Replace the entire housing, as the fans cannot be removed.
Motherboard faulty
You will need a second motherboard to make this diagnosis.
Disconnect the power from the unit.
Replace the motherboard with a new motherboard of the same type.
Restore the operating voltage and run the unit for a few minutes.
If the motherboard is faulty, the malfunction will no longer occur.
Replace the faulty motherboard.
The R3 potentiometer is moved to the setting for the pressure-dependent airflow
calibration.
Using a multimeter, measure the voltage (DC) at measuring points MP2 (x) and MP3
(-).
The default measurement value is 1.2 V. However, deviations may occur due to the
calibration of the airflow dependent on air pressure.
The measurement value must be between 0.5 V and 1.9 V. If the measured voltage
value is outside of this range, the R3 potentiometer setting is faulty.
Note: The malfunction only occurs at voltages below 0.2 V or above 2.3 V.
Using the R3 potentiometer, reset the voltage to a point between the measuring
points MP2 (x) and MP3 (-). 1.2 V for calibration independently of air pressure. In
accordance with the air pressure correction table for air-pressure-dependent
calibration.
Motherboard faulty
The voltage cannot be set in step 1.
Disconnect the power from the unit.
Remove the detector module's connection cables from the motherboard.
Restore the operating voltage and run the unit for a few minutes.
If the voltage at measuring points MP2 and MP3 cannot be set with the R3
potentiometer, the motherboard is faulty.
Note: If operating without a detector module, the diagnostics LED flashes 7 times.
Replace the faulty motherboard.
Detector module faulty
Disconnect the power from the unit.
Reconnect the connection cable for the first detector module to the motherboard.
Restore the operating voltage and run the unit for a few minutes.