en | Installation of the Pipe System
Positioning the air sampling opening depending on air
speed
6.4.2

Detection in the Bypass

Notice!
For detection in airflows ≥ 2 m/s, additionally feed the exhaust from the FCS-320 back into
the airflow area. Cut the end of the air-return pipe at an angle of 45°.
Positioning the air-return pipe – example with an air-
conditioning duct (bypass)
For details on connecting the air-return pipe, please see Air-return Pipe, page 98.
For FCS‑320 planning in these applications, see Planning for Forced Airflow, page 69.
See also
2018.04 | 2.0 | F.01U.130.926
1
2
3
1
3
Planning for Forced Airflow, page 69
Air-return Pipe, page 98
Planning for Forced Airflow, page 69
2
1/2 b
b
4
Operation Guide
Aspirating Smoke Detector
1
Aspiration pipe with air
sampling openings
2
Exhaust speed < 0.5 m/s
3
Exhaust speed > 0.5 m/s
1 Air-conditioning duct
2 Duct adapter
3 Aspiration
4 Air-return Pipe
b Width of air-conditioning duct
Bosch Sicherheitssysteme GmbH