Flashes - Error: Internal Voltage Monitoring; Flashes - Error: Fan Voltage Monitoring - Bosch FCS-320-TP2 Operation Manuals

Fcs-320 series. aspirating smoke detector
Hide thumbs Also See for FCS-320-TP2:
Table of Contents

Advertisement

Aspirating Smoke Detector
8.2.2

2 Flashes - Error: Internal Voltage Monitoring 2

In operation with two detector modules, both LEDs flash. When troubleshooting, the following
steps should be carried out in the specified order.
8.2.3

3 Flashes - Error: Fan Voltage Monitoring

In operation with two detector modules, both LEDs flash. When troubleshooting, the following
steps should be carried out in the specified order.
Bosch Sicherheitssysteme GmbH
Disconnect the power from the unit.
Remove the display board's connection cable from the motherboard.
Restore the operating voltage and run the unit for a few minutes.
If the display board is faulty, the malfunction will no longer occur.
Replace the faulty display board.
Motherboard faulty
You will need a second motherboard to make this diagnosis.
Disconnect the power from the unit.
Replace the motherboard with a new motherboard of the same type.
Restore the operating voltage and run the unit for a few minutes.
If the motherboard is faulty, the malfunction will no longer occur.
Replace the faulty motherboard.
Operating voltage too low
Using a multimeter, measure the operating voltage (DC) of the aspirating smoke
detector.
The measurement value must be between 14 V and 30 V.
Restore the correct power supply.
Detector module faulty
Disconnect the power from the unit.
Replace the detector module incl. connection cable with a new module of the same
type.
Restore the operating voltage and run the unit for a few minutes.
If the detector module is faulty, the malfunction will no longer occur.
If you are using two detector modules, repeat the process with the second detector
module.
Replace the faulty detector module.
Motherboard faulty
You will need a second motherboard to make this diagnosis.
Disconnect the power from the unit.
Replace the motherboard with a new motherboard of the same type.
Restore the operating voltage and run the unit for a few minutes.
If the motherboard is faulty, the malfunction will no longer occur.
Replace the faulty motherboard.
Operating voltage too low
Using a multimeter, measure the operating voltage (DC) of the aspirating smoke
detector.
The measurement value must be between 14 V and 30 V.
Restore the correct power supply.
Fan connection poles reversed
The fan does not move.
Disconnect the power from the unit.
Disconnect the fan connection cable from the motherboard.
Operation Guide
Maintenance | en 111
2018.04 | 2.0 | F.01U.130.926

Advertisement

Table of Contents
loading

Table of Contents