en | Installing the Aspirating Smoke Detector
Sensitivity
DM-TP-01(05)
DM-TT-01(05)
0.12%/m
(0.4%/m)
0.06%/m
(0.2%/m)
0.03%/m
(0.1%/m)
0.015%/m
(0.05%/m)
Alarm delay
0 seconds
10 seconds
30 seconds
60 seconds
Activation threshold for airflow malfunction
Low (+/- 10% volume flow change)
Average (+/- 20% volume flow change)
High (+/- 30% volume flow change)
Very high (+/- 50% volume flow change)
Airflow fault delay
30 seconds
2 minutes
15 minutes
60 minutes
Trouble logging
not saving
saving
2018.04 | 2.0 | F.01U.130.926
DM-TP10(25)
DM-TP50(80)
DM-TT-10(25)
DM-TT-50(80)
0.8%/m
-
(2%/m)
0.4%/m
-
(1%/m)
0.2%/m
1.0%/m
(0.5%/m)
(1.6%/m)
0.1%/m
0.5%/m
(0.25%/m)
(0.8%/m)
DIP settings
Switch 9
off
on
Operation Guide
Aspirating Smoke Detector
DIP settings
Switch 1
on
off
on
off
DIP settings
Switch 3
off
on
off
on
DIP settings
Switch 5
on
off
off
on
DIP settings
Switch 7
off
on
on
off
LOGIC·SENS filter
off
on
Bosch Sicherheitssysteme GmbH
Switch 2
on
on
off
off
Switch 4
off
off
on
on
Switch 6
off
on
off
on
Switch 8
on
off
on
off
DIP settings
Switch 10
off
on