Fas-Asd-Ws Water Separator - Bosch FCS-320-TP2 Operation Manuals

Fcs-320 series. aspirating smoke detector
Hide thumbs Also See for FCS-320-TP2:
Table of Contents

Advertisement

100 en | Installation of the Pipe System
6.8
FAS‑ASD‑WS Water Separator
FAS‑ASD‑WS Water Separator
The FAS‑ASD‑WS Water Separator must be fitted at the lowest point in the pipe system
downstream of the air filter and the aspirating smoke detector (see figure below).
2
Installing the FAS‑ASD‑WS Water Separator in the pipe
system
Connection
Attach two 45° pipe elbows on both sides (not supplied as standard) in order to achieve the
optimum distance from the wall for mounting the brackets. When installing, note the correct
direction of flow (see arrow on plastic container).
Also fasten the water separator with two screws and the clamp.
To empty, open the drain valve.
2018.04 | 2.0 | F.01U.130.926
Position the tap lever so that the blast air and pipe system are connected (B-C
connection).
The connection to the FCS-320 must be blocked for blowing-out!
Manually blow out the pipe system for approximately 10 seconds.
Set the lever of the tap such that the device is not connected with the pipe system or
with the connection for the blast or compressed air supply. Wait approximately 20
seconds so that dust and dirt raised in the pipe system can settle and thus will not be
sucked through the aspirating smoke detector.
Reconnect the blown-out pipe system to the FCS-320 within a further 10 seconds by
switching over the tap accordingly (A‑C connection).
3
3
1
Operation Guide
Aspirating Smoke Detector
1
FAS‑ASD‑WS Water
Separator
2
Pipe system connection
3
45° pipe elbow
Bosch Sicherheitssysteme GmbH

Advertisement

Table of Contents
loading

Table of Contents